Connecting IED with a test switch

When the IED is used with a test switch, connect the current and voltage
transformers directly to the switch.

Connecting binary signals

Each signal connector terminal is dimensioned for one 0.5...2.5 mm
2
two 0.5...1.0 mm
wires.
Table 12:
Binary inputs X304, 4U half 19" and 6U half 19"
Terminal
Description
X304-1
Common - for inputs 1-4
X304-2
Binary input 1 +
X304-3
Binary input 2 +
X304-4
Binary input 3 +
X304-5
Binary input 4 +
X304-6
Common - for inputs 5-8
X304-7
Binary input 5 +
X304-8
Binary input 6 +
X304-9
Binary input 7 +
X304-10
Binary input 8 +
X304-11
Common - for inputs 9-11
X304-12
Binary input 9 +
X304-13
Binary input 10 +
X304-14
Binary input 11 +
X304-15
Common - for inputs 12-14
X304-16
Binary input 12 +
X304-17
Binary input 13 +
X304-18
Binary input 14 +
Table 13:
Binary inputs X319, 4U half 19"
Terminal
Description
X319-1
- for input 1
X319-2
Binary input 1 +
X319-3
-
X319-4
Common - for inputs 2-3
Table continues on next page
Section 5
Connecting
2
wire or for
ACT info
Hardware module
Hardware channel
instance
COM_101
BI1
COM_101
BI2
COM_101
BI3
COM_101
BI4
COM_101
BI5
COM_101
BI6
COM_101
BI7
COM_101
BI8
COM_101
BI9
COM_101
BI10
COM_101
BI11
COM_101
BI12
COM_101
BI13
COM_101
BI14
ACT info
Hardware module
Hardware channel
instance
BIO_3
BI1
BIO_3
BI1
47