ABB 630 Series Manual
Hide thumbs Also See for 630 Series:

Advertisement

Quick Links

®
Relion
Protection and Control
630 series
DNP3 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB 630 Series

  • Page 1 ® Relion Protection and Control 630 series DNP3 Point List Manual...
  • Page 3 Document ID: 1MRS756791 Issued: 15.09.2009 Revision: A Product version: 1.0 © Copyright 2009 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Symbols and conventions..............6 Safety indication symbols..............6 Manual conventions...............6 Functions, codes and symbols............7 Section 2 DNP3 data mappings.............11 Overview...................11 Point list for 630 series IEDs ............11 Section 3 DNP3 protocol implementation........41 DNP3 device profile................41 DNP3 implementation table..............44 Section 4 Glossary.................49 630 series...
  • Page 9: Section 1 Introduction

    IED perspective. The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. 630 series Point List Manual...
  • Page 10: Product Documentation

    The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as well as verifying settings by secondary injection. The manual describes the process 630 series Point List Manual...
  • Page 11: Document Revision History

    The service manual is not available yet. 1.3.2 Document revision history Document revision/date Product version History A/2009.09.15 First release Download the latest documents from the ABB web site http:// www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual...
  • Page 12: Symbols And Conventions

    The * character after an input or output signal name in the function block symbol given for a function, indicates that the signal must be connected to another function block in the application configuration to achieve a valid application configuration. 630 series Point List Manual...
  • Page 13: Functions, Codes And Symbols

    Section 1 1MRS756791 A Introduction 1.4.3 Functions, codes and symbols Table 1: Functions included in 630 series IEDs Functionality IEC 61850 IEC 60617 ANSI Protection Three-phase non-directional overcurrent, PHLPTOC 3I> 51P-1 low stage Three-phase non-directional overcurrent, PHHPTOC 3I>> 51P-2 high stage...
  • Page 14 MCS 3I MCS 3I Trip-circuit supervision TCSSCBR Generic measured values MVGGIO Measured value limit supervision MVEXP Station battery supervision SPVNZBAT U<> U<> Tap position indication TPOSSLTC TPOSM Energy monitoring EPDMMTR Table continues on next page 630 series Point List Manual...
  • Page 15 A3RADR ACH3 ACH3 Analog channel 31-40 (calc. val.) A4RADR ACH4 ACH4 Binary channel 1-16 B1RBDR BCH1 BCH1 Binary channel 17-32 B2RBDR BCH2 BCH2 Binary channel 33-48 B3RBDR BCH3 BCH3 Binary channel 49-64 B4RBDR BCH4 BCH4 630 series Point List Manual...
  • Page 17: Section 2 Dnp3 Data Mappings

    This list represents the superset of DNP3 points. The actual set of available points depends on the product, optional functionalities and configuration. See the engineering manual and DNP3 communication protocol manual for more information. Point list for 630 series IEDs Table 2: Signal point list Function name...
  • Page 18 CMMXU.1.I_DB_B Phase B amplitude, magnitude of reported value CMMXU.1.I_DB_C Phase C amplitude, magnitude of reported value CMMXU.1.I_ANGL_A Phase A angle, instantaneous value CMMXU.1.I_ANGL_B Phase B angle, instantaneous value Table continues on next page 630 series Point List Manual...
  • Page 19 Fault Freq DNPFREC.1.Fault Location Fault Location DNPFREC.1.Fault Number Fault Number DNPFREC.1.Fault Type Fault Type DNPFREC.1.No of faults in IED No of faults in IED DNPFREC.1.Trig Signal Id Trig Signal Id Table continues on next page 630 series Point List Manual...
  • Page 20 DNPFREC.1.Sig5 Fault Angle Fault Angle DNPFREC.1.Sig5 Fault Fault Magnitude Magnitude DNPFREC.1.Sig5 Prefault Prefault Angle Angle DNPFREC.1.Sig5 Prefault Prefault Magnitude Magnitude DNPFREC.1.Sig6 Fault Angle Fault Angle DNPFREC.1.Sig6 Fault Fault Magnitude Magnitude Table continues on next page 630 series Point List Manual...
  • Page 21 DNPFREC.1.Sig11 Prefault Prefault Magnitude Magnitude DNPFREC.1.Sig12 Fault Angle Fault Angle DNPFREC.1.Sig12 Fault Fault Magnitude Magnitude DNPFREC.1.Sig12 Prefault Prefault Angle Angle DNPFREC.1.Sig12 Prefault Prefault Magnitude Magnitude DNPFREC.1.Sig13 Fault Angle Fault Angle Table continues on next page 630 series Point List Manual...
  • Page 22 DNPFREC.1.Sig18 Prefault Prefault Angle Angle DNPFREC.1.Sig18 Prefault Prefault Magnitude Magnitude DNPFREC.1.Sig19 Fault Angle Fault Angle DNPFREC.1.Sig19 Fault Fault Magnitude Magnitude DNPFREC.1.Sig19 Prefault Prefault Angle Angle DNPFREC.1.Sig19 Prefault Prefault Magnitude Magnitude Table continues on next page 630 series Point List Manual...
  • Page 23 DNPFREC.1.Sig25 Fault Fault Magnitude Magnitude DNPFREC.1.Sig25 Prefault Prefault Angle Angle DNPFREC.1.Sig25 Prefault Prefault Magnitude Magnitude DNPFREC.1.Sig26 Fault Angle Fault Angle DNPFREC.1.Sig26 Fault Fault Magnitude Magnitude DNPFREC.1.Sig26 Prefault Prefault Angle Angle Table continues on next page 630 series Point List Manual...
  • Page 24 DNPFREC.1.Sig36 Magnitude Magnitude at trig at trig DNPFREC.1.Sig37 Magnitude Magnitude at trig at trig DNPFREC.1.Sig38 Magnitude Magnitude at trig at trig DNPFREC.1.Sig39 Magnitude Magnitude at trig at trig Table continues on next page 630 series Point List Manual...
  • Page 25 Analog inputs DSTPDIS.1.DIR_E_FLT Earth-fault direction (low imp. earthed), GFC DSTPDIS.1.CONFLICT_Z1 Tilt angle validity check, Zone Z1 DSTPDIS.1.CONFLICT_Z2 Tilt angle validity check, Zone Z2 DSTPDIS.1.CONFLICT_Z3 Tilt angle validity check, Zone Z3 Table continues on next page 630 series Point List Manual...
  • Page 26 Record data of bank 1 for direction resistance, Zone Z3 DSTPDIS.1.2 DIR_LOOP_R Record data of bank 2 for direction resistance, Zone AR1 DSTPDIS.1.2 DIR_LOOP_R Record data of bank 2 for direction resistance, Zone AR2 Table continues on next page 630 series Point List Manual...
  • Page 27 (1st), Zone Z2 DSTPDIS.1.3 FLTLOOP_XFST Record data of bank 3 for PE- loop reactance (1st), Zone Z3 DSTPDIS.1.1 FLTLOOP_XSND Record data of bank 1 for PE- loop reactance (2nd), Zone AR1 Table continues on next page 630 series Point List Manual...
  • Page 28 (1st), Zone Z1 DSTPDIS.1.2 FLTLOOP_RFST Record data of bank 2 for PE- loop resistance (1st), Zone Z2 DSTPDIS.1.2 FLTLOOP_RFST Record data of bank 2 for PE- loop resistance (1st), Zone Z3 Table continues on next page 630 series Point List Manual...
  • Page 29 Zone AR2 DSTPDIS.1.1 FLTLOOP_XPP Record data of bank 1 for PP- loop reactance, Zone Z1 DSTPDIS.1.1 FLTLOOP_XPP Record data of bank 1 for PP- loop reactance, Zone Z2 Table continues on next page 630 series Point List Manual...
  • Page 30 Zone AR1 DSTPDIS.1.3 FLTLOOP_RPP Record data of bank 3 for PP- loop resistance, Zone AR2 DSTPDIS.1.3 FLTLOOP_RPP Record data of bank 3 for PP- loop resistance, Zone Z1 Table continues on next page 630 series Point List Manual...
  • Page 31 Event release phase A to earth fault DSTPDIS.1.RELEASE_B Event release phase B to earth fault DSTPDIS.1.RELEASE_C Event release phase C to earth fault DSTPDIS.1.RELEASE_AB Event release phase A to phase Table continues on next page 630 series Point List Manual...
  • Page 32 Event start phase A, Zone AR2 DSTPDIS.1.ST_ZAR2_B Event start phase B, Zone AR2 DSTPDIS.1.ST_ZAR2_C Event start phase C, Zone AR2 DSTPDIS.1.1 EARTH_FLT GFC Record data of bank 1 for earth- fault, GFC Table continues on next page 630 series Point List Manual...
  • Page 33 Residual current (RESCMMXU) Analog inputs RESCMMXU.1.I0_DB Residual current RMS, magnitude of reported value RESCMMXU.1.I0_ANGL Residual current angle Residual voltage (RESVMMXU) Analog inputs RESVMMXU.1.U0_MAG_DB U0 Amplitude, magnitude of reported value Table continues on next page 630 series Point List Manual...
  • Page 34 Operate Signal Phase discontinuity Binary inputs PDNSPTOC.1.START Phase discontinuity protection (PDNSPTOC) started PDNSPTOC.1.OPERATE Phase discontinuity protection operated. Three-phase thermal overload Binary inputs T1PTTR.1.OPERATE Operate Signal for feeder (T1PTTR) T1PTTR.1.START Start Signal Table continues on next page 630 series Point List Manual...
  • Page 35 (DPHLPDOC) DPHLPDOC.1.OPERATE Operated DPHLPDOC.1.FAULT_DIR Detected fault direction, general DPHLPDOC.1.ST_A Started phase A DPHLPDOC.1.ST_B Started phase B DPHLPDOC.1.ST_C Started phase C DPHLPDOC.1.OPR_A Operated phase A DPHLPDOC.1.OPR_B Operated phase B Table continues on next page 630 series Point List Manual...
  • Page 36 SCEFRFLO.1.1 A Pre angle PhA Record data of bank 1 for phase A pre-fault current angle SCEFRFLO.1.1 A Pre angle PhB Record data of bank 1 for phase B pre-fault current angle Table continues on next page 630 series Point List Manual...
  • Page 37 SCEFRFLO.1.1 PhV Pre value Record data of bank 1 for phase A pre-fault voltage amplitude SCEFRFLO.1.1 PhV Pre value Record data of bank 1 for phase B pre-fault voltage amplitude Table continues on next page 630 series Point List Manual...
  • Page 38 Restore signal for load restoring purposes LSHDPFRQ.1.ST_REST Restore frequency attained and restore timer started LSHDPFRQ. Signal indicating internal 1.LOWAMPL_BLKD blocking due to low amplitude LSHDPFRQ.1.OPR_FRQ Operate signal for under frequency Table continues on next page 630 series Point List Manual...
  • Page 39 Reclosing sequence is in progress DARREC.1.INPRO_1 Reclosing shot in progress, shot 1 DARREC.1.INPRO_2 Reclosing shot in progress, shot 2 DARREC.1.INPRO_3 Reclosing shot in progress, shot 3 DARREC.1.INPRO_4 Reclosing shot in progress, shot 4 Table continues on next page 630 series Point List Manual...
  • Page 40 SYNCRSYN.1.B2_SEL Bus2 selected SYNCRSYN.1.LN1_SEL Line1 selected SYNCRSYN.1.LN2_SEL Line2 selected Bay control (QCCBAY) Binary inputs QCCBAY.1.UPD_BLKD Update of position is blocked QCCBAY.1.CMD_BLKD Function is blocked for commands QCCBAY.1.LOC Local operation allowed Table continues on next page 630 series Point List Manual...
  • Page 41 CB is in invalid position (not positively open or closed) SSCBR.1.IPOW_ALM Accumulated currents power (Iyt),exceeded alarm limit SSCBR.1.IPOW_LO Accumulated currents power (Iyt),exceeded lockout limit SSCBR.1.MON_ALM CB 'not operated for long time' alarm Table continues on next page 630 series Point List Manual...
  • Page 42 CRWPSCH.1.ECHO Carrier send by WEI logic CRWPSCH.1.CR POR Carrier signal received from remote end Energy monitoring (EPDMMTR) Analog inputs EPDMMTR.1.EAFALM Alarm for active forward energy exceed limit in set interval Table continues on next page 630 series Point List Manual...
  • Page 43 2 winding phases, both stages) transformers (TR2PTDF) TR2PTDF.1.OPR_A Operate signal phase A TR2PTDF.1.OPR_B Operate signal phase B TR2PTDF.1.OPR_C Operate signal phase C TR2PTDF.1.BLKD2H Status from 2nd harmonic restraint block, combined Table continues on next page 630 series Point List Manual...
  • Page 44 Low impedance restricted earth- fault protection operate LREFPNDF.1.BLK2H Signal to indicate second harmonic blocking when the second harmonic has been enabled Emergency start (ESMGAPC) Binary inputs ESMGAPC.1.ST_EMERG_ENA Emergency start signal Table continues on next page 630 series Point List Manual...
  • Page 45 Operate signal INTRPTEF.BLK_EF Block signal for EF to indicate opposite direction peaks Versatile Switch (VSGGIO) Binary inputs VSGGIO.1.POS1 Position 1 indication, logical signal VSGGIO.1.POS2 Position 2 indication, logical signal Double bit indications VSGGIO.1.POSITION Position indication, integer 630 series Point List Manual...
  • Page 47: Section 3 Dnp3 Protocol Implementation

    Table 3: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: 630 series IED Highest DNP level supported: Device function: For requests: Level + ○ Master For responses: Level + ●...
  • Page 48 ● Always ○ Sometimes ○ Configurable OPERATE DIRECT ○ Never ○ Always ○ Sometimes ● Configurable OPERATE DIRECT ○ Never ○ Always ○ Sometimes ● Configurable OPERATE - NO ACK Table continues on next page 630 series Point List Manual...
  • Page 49 Configurable (ApplMultFrgRes on DNP3Master) Deadbanding is not performed in the DNP protocol stack. Any deadbanding is a property of the IED’s underlying data, and is configured through the IED configuration tools. ● = Selected,○ = Not selected 630 series Point List Manual...
  • Page 50: Dnp3 Implementation Table

    07, 08 (limited qty) 130 (unsol. resp) Double bit input 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) change with relative 07, 08 (limited qty) 130 (unsol. resp) time Table continues on next page 630 series Point List Manual...
  • Page 51 07, 08 (limited qty) 130 (unsol. resp) 16–bit counter change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) event with time 07, 08 (limited qty) 130 (unsol. resp) Table continues on next page 630 series Point List Manual...
  • Page 52 130 (unsol. resp) with time Time and date Time and date 1 (read) 07, (limited qty = 1) 129 (response) 07 (limited qty = 1) 2 (write) 07, (limited qty = 1) Table continues on next page 630 series Point List Manual...
  • Page 53 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.) 3) Writes of internal indications are only supported for index 7 (Restart IIn1–7) 630 series Point List Manual...
  • Page 55: Section 4 Glossary

    Parameter Setting Tool in PCM600 REF630 Feeder protection and control IED REM630 Motor protection and control IED RET630 Transformer protection and control IED Root-mean-square (value) SOTF Switch on to fault Trip-circuit supervision Weak-end infeed logic 630 series Point List Manual...
  • Page 60 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...