ABB 630 series Installation Manual page 36

Hide thumbs Also See for 630 series:
Table of Contents

Advertisement

Section 4
Mounting
28
8.1. Use a 16.0 mm
2
flat braided copper cable.
8.2. Insert the M5 GND screw with a washer trough the grounding clamp
and ground cable.
Use a GND screw that is equal or shorter than the thickness of the
washer, grounding clamp, braided copper cable and panel +4 mm.
8.3. Use a spring lock washer.
8.4. Connect the other end of the ground cable to the cabinet door as near as
possible to the LHMI ground.
8.5. Tighten the GND screws.
1
2
GUID-ED1F1C7D-46A7-4EDE-820C-BEDD8FBCAFAA V2 EN
Figure 13:
LHMI grounding
1 Surface coating removed ∅15 mm
2 Ground cable
3 M5 screw and washer for grounding LHMI and cable to the panel
1MRS755958 C
3
630 series
Installation Manual

Advertisement

Table of Contents
loading

Table of Contents