Chapter 6 - Commissioning

Commissioning the Drive

64 | 82
Siemens Industry, Inc.
Building Technologies
DANGER
Always ensure absence of voltage before starting any electrical work!
After disconnecting the drive from line voltage, wait until the indicators on the keypad
go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes
before doing any work on the connections of the BT300 Drive. Do not open the cover
before this time has expired. After expiration of this time, use a measuring equipment
to absolutely ensure that no voltage is present.
Veuillez vous assurer en toute circonstance que la tension d'alimentation est coupée
avant tout raccordement électrique.
Après avoir débrancher le variateur de la tension de ligne, vous devez attendre
l'extinction des voyants sur le panneau opérateur (si aucun panneau opérateur n'est
raccordé, voir les voyants sur le capot). Attendez cinq minutes supplémentaires avant
de commencer tout travail sur les bornes du variateur Siemens BT300. Ne pas ouvrir
le capot avant la fin de cette période d'attente. À l'expiration de cette période, utilisez
un instrument de mesure pour vous assurer qu'aucune tension n'est présente.
DANGER
Before connecting the drive to the primary input voltage make sure that the front and
cable covers of the BT300 Drive are closed.
Avant de brancher le variateur à la tension de ligne, assurez-vous que les capots
avant et de câblage du variateur Siemens BT300 sont fermés.
NOTICE
Corner grounding is allowed for the drive types with ratings from 72 A to 310 A at
380V through 480V supply and from 75A to 310A at 208V through 240V supply.
Remember to change the EMC level by removing the jumpers. See Chapter 6.3
[➙ 66].
NOTE:
R+ and R- terminals are not used in the Siemens BT300 Drive and external
components must not be connected to them.
Commissioning the Drive
Carefully read the safety instructions in Chapter 1 and above information and follow
them.
After the installation:
Before connecting the drive to mains: Check mounting and condition of all fuses
and other protective devices.
Check that both the drive and the motor are grounded.
Check that the mains and motor cables comply with the requirements given in
Chapter 4.1.1.
Siemens BT300 HVAC Drive Installation
Instructions
DPD01148
2016-06-28