Chapter 6 - Commissioning
Installation in an IT System
70 | 82
Siemens Industry, Inc.
Building Technologies
Figure 56: Removing the Jumper, FS6 as Example.
Frames FS7 and FS8
Use the procedure in this section to modify the EMC protection of the drive of frames
FS7 and FS8 to EMC-level C4.
1. Remove the main cover of the drive and locate the jumper. FS8 only: Push down
the grounding arm. See the following figure.
Figure 57: Grounding Arm, FS8.
Siemens BT300 HVAC Drive Installation
Instructions