High Elevation; Gas Line Installation; Copreci Valve Description; Aeration Adjustment - Regency Plateau Owners And Installation Manual

Table of Contents

Advertisement

installation
|
10
PTO28 - NG1 SYSTEM DATA
Max. Supply Pressure
14" WC (3.49 kPa)
Min. Supply Pressure
5" WC (1.25 kPa)
Manifold Pressure -High 3.5" WC (0.87 kPa)
Manifold Pressure- Low
0.5" WC (0.12 kPa)
Orifice Size
#32 DMS
Maximum Input
33,500 Btu/h
(9.82 kW)
Minimum Input
13,000 Btu/h
(3.80 kW)
PTO28 - LP1 SYSTEM DATA
Max. Supply Pressure
14" WC (3.49 kPa)
Min. Supply Pressure
12" WC (2.99 kPa)
Manifold Pressure- High 11" WC (2.74 kPa)
Manifold Pressure- Low
1" WC (0.25 kPa)
Orifice Size
#50 DMS
Maximum Input
35,000 Btu/h
(10.26 kW)
Minimum Input
11,000 Btu/h
(3.23 kW)

HIGH ELEVATION

This unit is approved for altitude 0 to 4500 ft. (CAN/
CGA 2.17-M91).
GAS LINE
INSTALLATION
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or flex connectors use only
approved fittings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and flex connectors are
usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open flame for leak testing.
NOTE: This is a low pressure system. Pressure
in excess of 14" will require a pressure regulator
to reduce gas flow to appliance.
10 |
Regency PTO28-1 City Table Outdoor Gas Fireplace
COPRECI VALVE
DESCRIPTION
1. Push nozzle
2. Main gas outlet
3. Main gas inlet
4. Thermocouple connection
1
2
4

AERATION ADJUSTMENT

The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue flame or
close for a more yellow flame.
Follow steps 1-4 in LP -NG conversion in this
manual.
Minimum Air Shutter Opening:
Fully Closed
Fully Open
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from supplied regulator at pressures over 1/2 psig.
Note: To properly check the inlet pressure, use
1. Make sure the valve is in the "OFF" position.
3
2. Loosen the pressure tap, turning counterclock-
wise with a 1/8" wide flat screwdriver.
3. Attach manometer to pressure tap using a 5/16"
ID hose.
4. Light the unit (see Lighting instructions).
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6. When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not over
tighten.
NG
LP
the regulator pressure tap (see P.15).