Label Number Guide For Figure 1 - ABB REB500 Applications Manual

Bay protection functions
Hide thumbs Also See for REB500:
Table of Contents

Advertisement

Section 2
Overview
2.2.2
8

Label number guide for Figure 1

Table 2
Explanations to inputs / outputs
Item No.
Name
Definition
1
OC input
Optocoupler input of bay unit
2
CR output
Relay (contact) output of bay
unit
3
U, I input
Analog input of bay unit
4
BP input
Logical input of BP part
5
BP output
Logical output of BP part
Table 3
Explanations to protection function part
Label No.
Name
6
SP
SP function
7
BP
BP function
Table 4
Explanations to signal connections
Label No.
Definition
8
OC input assigned to SP function
9
SP function assigned to CR output
10
OC input assigned to BP input
11
BP input assigned to BP function
12
BP function assigned to BP output
13
BP-output assigned to CR output
14
BP-output assigned to SP function
15
SP-function assigned to BP input
16
OC-input assigned to SP function and BP
input
17
SP function and BP output assigned to CR
output
18
Internal connections between BP-functions
19
Internal connections between SP-functions
Definition
Station protection part
Station protection function
Bay protection part
Bay protection function
1MRK 505 353-UEN
Remark
33 binary inputs per bay unit
19 binary outputs per bay unit
Assignment to SP functions is fixed.
Assignment to BP functions is partly
configurable.
20 logical inputs per bay unit
120 logical outputs per bay unit
Remark
Contains station protection functions
Available functions
e.g. BBP, BFP, EFP, ..
Contains bay protection functions
Available functions
e.g. DIST, OCDT, ..
Remark
Assignment via software HMI500
e.g. 13710_Start BFP_L1_1
Assignment via software HMI500
e.g. 23105_BFP TRIP
Assignment via software HMI500
e.g. 111205_DIST Ext. Block Dist.
Assignment via software HMI500
e.g. DIST: Ext Blk Dist
Assignment via software HMI500
e.g. DIST: Com Send
Assignment via software HMI500
e.g. 211880_ DIST Com
Assignment via software HMI500
e.g. DIST: Trip_DIST à 13785_BP Start
BFP L1L2L3
Assignment via software HMI500
Assignment via software HMI500
e.g. 11530/ 118515_Q0 Open and CB
OPEN
Assignment via software HMI500
e.g. 21110/ 220815_TRIP
Assignment via software HMI500
Automatic assignment done by REB500
ITT-system
(ITT = intertripping)
Application Manual
Bay protection functions REB500

Advertisement

Table of Contents
loading

Table of Contents