Mitsubishi FX2N-10PG Installation Manual page 8

Melsec-f, pulse generator block

Advertisement

2.1 Applicable PLC
Series name
Applicable version
FX
series
All versions (First release).
2N
FX
series
All versions (First release).
2NC
FX
series
All versions (First release).
3U
FX
series
All versions (First release).
3UC
3. Installation
Caution
1) Do not lay signal cable near to high voltage power cable or house them in the same trunking
duct. Effects of noise or surge induction may occur. Keep signal cables a safe distance of more
than 100 mm (3.94") from these power cables.
2) Ground the shied wire or the shield of a shielded cable at one point on the PLC.
Do not, however, ground at the same point as high voltage lines.
3) Cut off all phases of power source before installing / removing or performing wiring work on the
unit in order to avoid electric shock or damage of product.
4) Replace the provided terminal cover before supplying power and operating the unit after
installation or wiring work, in order to avoid electric shock.
3.1 Mounting
The FX
-10PG can be DIN rail direct wall mounted.
2N
1) DIN rail mounting
a)
Align the upper side of the DIN rail mounting groove of the FX
2N
DIN rail( ). See Figure 3.1.
b)
When removing the FX
-10PG from the DIN rail, the hook for DIN rail is pulled ( ), and the FX
2N
removed ( ). See Figure 3.1.
*1 Uses DIN 46277 <35mm (1.38")>
Attach to DIN Rail and Remove from DIN Rai

2) Direct mounting to back walls
The FX
-10PG can be mounted with M4 screws, using the direct mounting holes.
2N
An interval space between each unit of 1-2 mm is necessary.
4. Specifications
4.1 General Specifications
General Specifications
Items
Specifications
Items other than the
Same as general specification of the PLC main unit.
following
(Refer to the PLC MANUAL)
Dielectric with stand
AC 500V 1 minute (between each terminal and earth terminal)
voltage
4.2 Power Supply Specifications
Power Supply Specifications
Items
Input
signal
Power
supply
Internal
control
Output
signal
Refer to the USER'S MANUAL for the performance specification and the I/O specification.
5. Diagnostics
5.1 Preliminary Checks
Check Wiring and Program of the PLC main unit when FX
FX
-10PG will not operate normally if the FROM/TO instruction is executed when an abnormality occurs in
2N
the PLC main unit.
Correspond according to the content when an abnormality occurs in the main unit (off POWER LED and
*1
-10PG with a DIN rail
( ), and push it on the
blinking ERROR LED/Lit ERROR LED). (Refer to the HARDWARE MANUAL, PROGRAMMING MANUAL ΙΙ
for PLC)
-10PG is
2N
ERROR LED is lit when an operation error occurs in the PLC main unit while turned off. (The instruction
where the operation error occurs is not executed.)
Check the ON/OFF status of M8067 with external programming equipment, and correct any errors.
5.2 LED check
LED
State
name
display
OFF/
POWER
Blinking
START
OFF
ƒ
Blinking
ERROR
FP
OFF
RP
OFF
OFF
CLR
DOG
OFF
PG0
OFF
Specifications
START,DOG,X0,X1: 24V DC +10% -10%. Consumption current 32mA or less.
PG0, φA, φB: 3 to 5.5V DC. Consumption current 20mA or less.
VIN: 5 to 24V DC. The consumption current when the power supply is used 5V
DC is 100mA or less.
The consumption current when the power supply is used 24V DC is 70mA or
less.
Power from external power supply.
START,DOG,X0,X1 can connect service power supply of programmable
controller main unit (24+ terminal)
5V DC consumption current 120mA from PLC main unit.
FP, RP (Supply the power supply by the terminal of VIN. 5 to 24V DC): Have
the current to 25mA or less.
CLR: 5 to 24V DC have the consumption current to 20mA or less. Power from
servo amplifier or external power supply
-10PG does not operate normally.
2N
Measures
When the LED does not lit even if the power supply is supplied PLC.
• Connect the extension cable between the PLC main unit and FX
correctly.
• Supply power to the PLC main unit correctly.
• PLC service power supply capacity is exceeded.
• Remove wiring from the terminal of the service power supply.
At START input ON.
• Check the input wiring. An external power supply is necessary for the
terminal START. (24V DC)
• Error occurs in FX
-10PG. Do measures corresponding to the content after
2N
checking the content of buffer memory (BFM#37).
Refer to Specific manual name for details of BFM#37.
Lit
• Please contact a service representative.
When output forward pulses and reverse pulses.
• Dependent on PLC program, start each drive or check.
• Do not output the pulse when there are stop, forward limit, and reversal limit
instruction.
When Home position return is completed.
• Home position return drive, the data set type Home position return, and the
compulsion output of the CLR signal must be executed by programming the
PLC main unit or check.
When a clear signal is not input with the servo amplifier.
• Check the output wiring.
Lit
An external power supply is necessary for the terminal CLR output (5 to 24V
DC).
At DOG input ON.
• Check the input wiring. An external power supply is necessary for the
terminal DOG. (24V DC).
At PG0 input ON.
• Check the input wiring. When NPN/PNP opening collector transistor is used,
an external power supply is necessary for the terminal PG0. (5V DC).
LED
State
name
display
At φA, φB input ON.
φA
OFF
• Check the input wiring. When manual pulse generator of opening collector
output type is used, an external power supply is necessary for the terminals
φB
OFF
φA, φB (5V DC).
At X0,X1 input ON.
X0,X1
OFF
• Check the input wiring. An external power supply is necessary for the
terminal
X0,X1
(24V DC).
「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称, 含有量, 含有部品
 
本产品中所含有的有害 6 物质的名称, 含有量, 含有部品如下表所示。
产品中有害物质的名称及含量
部件名称
(Pb)
(Hg)
外壳
可编程控制器
印刷基板
×
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T 26572规定的限量要求。
-10PG
2N
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any
patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving
industrial property rights which may occur as a result of using the contents noted in this manual.
Manual number : JY992D91901
Manual revision : E
Date
HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
JY992D91901E
Measures
有害物质
六价铬
多溴联苯
多溴二苯醚
(Cd)
(Cr(VI))
(PBB)
(PBDE)
: August 2017
Effective August 2017
Specifications are subject to
change without notice