Channel Configuration Examples - ABB UNO-DM-TL-PLUS-US Product Manual

From 3.3 to 5.0 kw
Table of Contents

Advertisement

Channel configuration examples

PV generator characteristics
The photovoltaic generator consists
of strings having a different number
of modules in series from each other.
The photovoltaic generator consists
of strings that have different installa-
tion conditions from each other.
The photovoltaic generator consists
of strings having the same number
of modules in series as each other.
The photovoltaic generator consists
of strings that have the same instal-
lation conditions, that is to say, all
the strings have the same inclination
from the horizontal and the same
orientation to the SOUTH.
The photovoltaic generator con-
nected to each of the inputs has a
power lower than the power limit
of the input channel AND a current
lower than the current limit of the
input channel.
(*) This condition is advisable from the point of view of the energy production of the system, not from the
point of view of inverter operation.
The photovoltaic generator consists
of strings having the same number
of modules in series as each other.
The photovoltaic generator consists
of strings that have the same instal-
lation conditions, that is to say, all
the strings have the same inclination
from the horizontal and the same
orientation to the SOUTH.
The photovoltaic generator con-
nected to each of the inputs has a
power higher than the power limit
of the input channel OR a current
higher than the current limit of the
input channel.
(*) This condition is sufficient from the point of view of the energy production of the system, not from the point
of view of inverter operation.
(**) This condition is advisable from the point of view of the energy production of the system, not from the
point of view of inverter operation.
MPPT configu-
ration
A NECESSARY condition so that the two
MPPTs can be used in independent mode is for
MPPT
the photovoltaic generator connected to each
configuration
of the inputs to have a power lower than the
has to be
power limit of the single input channel AND a
INDEPENDENT
maximum current lower than the current limit of
the single input channel.
A NECESSARY condition so that the two
MPPTs can be used in independent mode is for
the photovoltaic generator connected to each
Possibility
of the inputs to have a power lower than the
of choosing
power limit of the input channel AND a maxi-
between the
mum current lower than the current limit of the
configuration
input channel.
with MPPT as
An ADVISABLE (*) condition so that the two
INDEPENDENT
MPPTs can be connected in parallel is for the
or
photovoltaic generator connected to the two
PARALLEL
inputs to consist of strings made by the same
number of modules in series and for all the
modules to have the same installation condi-
tions.
A SUFFICIENT (*) condition so that the two
MPPTs must be used in parallel mode is for
the photovoltaic generator connected to each
of the inputs to have a power higher than the
power limit of the single input channel OR a
MPPT
maximum current higher than the current limit
configuration
of the single input channel.
has to be
An ADVISABLE (**) condition so that the two
PARALLEL
MPPTs can be connected in parallel is for the
photovoltaic generator connected to the two
inputs to consist of strings made by the same
number of modules in series and for all the
modules to have the same installation condi-
tions.