ABB i-bus KNX Product Manual page 213

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
929, 932... Em lighting test result
This group object is enabled if there is an Emergency light x enabled in X lighting converter/Emergency light template
parameter window, p. 155 and the Enable Group objects "Em lighting test result" parameter is set to Yes in the A lighting
converter, Emergency light x parameter window.
This group object transmits the result of an emergency lighting test for emergency lighting converter x on the KNX.
The information is transmitted in a 6-byte group object with the following coding:
The coding is based on numeric values generated from bit fields of various lengths:
LTRF Result of last function test (4-bit numeric value 0...15)
6 - 15 = Reserved, no function
LTRD Result of last duration test (4-bit numeric value 0...15)
6 - 15 = Reserved, no function
LTRP Result of last partial duration test (4-bit numeric value 0...15)
6 - 15 = Reserved, no function
SF Method used to trigger last function test (2-bit numeric value 0...3)
SD Method used to trigger last duration test (2-bit numeric value 0...3)
SP Method used to trigger last partial duration test (2-bit numeric value 0...3)
LDTR corresponds to the discharge time after a duration test pass (DALI 243) (2-byte DPT 7.006)
LPDTR corresponds to battery charge (DALI 241) (1-byte, unsigned)
Function
0 = Reserved, no function
1 = Function test passed within execution time
2 = Function test passed but not within execution time
3 = Function test failed
4 = Function test failed. Result determined outside execution time
5 = Function test stopped manually
0 = Reserved, no function
1 = Duration test passed within execution time
2 = Duration test passed but not within execution time
3 = Duration test failed
4 = Duration test failed. Result determined outside execution time
5 = Duration test stopped manually
0 = Reserved, no function
1 = Partial duration test passed within execution time
2 = Partial duration test passed but not within execution time
3 = Partial duration test failed
4 = Partial duration test failed. Result determined outside execution time
5 = Partial duration test stopped manually
0 = Reserved, no function
1 = Automatically triggered by emergency lighting converter
2 = Triggered by gateway
3 = Reserved, no function
0 = Reserved, no function
1 = Automatically triggered by emergency lighting converter
2 = Triggered by gateway
3 = Reserved, no function
0 = Reserved, no function
1 = Automatically triggered by emergency lighting converter
2 = Triggered by gateway
3 = Reserved, no function
Coding corresponds to KNX DTP 7.006 (2-byte). The time is given in minutes.
Maximum time is 510 min even if a longer time is available.
0, corresponds to discharged battery
254, corresponds to fully charged battery
255, emergency lighting converter does not support the Battery charge state status function
1)
Execution Time: Time within which an emergency lighting test has to run. This time is stored in the emergency lighting
converter and can be set via the Time limit for triggering emergency lighting test parameter in the Emergency light x
parameter window.
Group object name
Output A - Emergency light x
1)
1)
1)
.
1)
1)
1)
.
1)
1)
1)
.
DG/S x.64.1.1 | 2CDC507164D0201 211
Data type
Flags
6 byte
C, R, T
DPT_CTR