ABB i-bus KNX Product Manual page 190

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
22
This group object is enabled if Enable Group object "Number of faults statistic" is set to Yes in X Output: Fault parameter
window, p. 57.
This group object consists of 4 bytes. The individual bytes contain the number of faults on output A as a whole.
The following numbering applies to the list below:
31
2
15
2
The bit number is identical to the exponent of the bit, e.g. number 2 corresponds to 2
Bit 0 to 5
Bit 6
Bit 7
Bit 8 to 13
Bit 14
Bit 15
Bit 16 to 21
Bit 22
Bit 23
Bit 24 to 29
Bit 30
Bit 31
The telegrams are sent as soon as the fault is detected. Should several faults occur at the same time, the telegrams are sent
consecutively on the KNX. If a fault is corrected, this is also signaled on the group object.
Note: Depending on the situation and parametrization, it can take some time to detect fault status.
23
This group object is enabled if the Enable Group object "Number of ballast faults" parameter is set to Yes in the X Output:
Fault parameter window, p. 57.
This group object displays the number of individual DALI devices with at least one lamp or ballast fault (referred to on an
emergency lighting converter as a converter fault). The value of the group object is sent on the KNX whenever a change
occurs.
Telegram value:
If there is a ballast fault, this is not simultaneously signaled as a lamp fault.
188 2CDC507164D0201 | DG/S x.64.1.1
Function
Number of faults statistic
Dependent on parameter
30
29
28
27
26
25
2
2
2
2
2
2
14
13
12
11
10
9
2
2
2
2
2
2
= Number of ballasts on the output which are currently signaling on the DALI (without emergency lighting
converters)
= 0, without function
= 0, without function
= number of emergency lighting converters on the output (without ballasts) which are signaling the DALI.
= 0, without function
= 0 = all emergency lighting converters are ok
= 1 = at least one emergency lighting converter has a hardware fault
= number of lamp faults on the output
= 0 = none of the emergency lighting converters has signaled a lamp fault
= 1 = at least one emergency lighting converter has signaled a lamp fault
= 0 = none of the ballasts has signaled a lamp fault
= 1 = at least one of the ballasts has signaled a lamp fault
= number of malfunctioning DALI devices on the output (without ballasts and emergency lighting
converters) which are no longer signaling on the DALI. DALI device monitoring is required.
= 0 = none of the emergency lighting converters have a ballast fault
= 1 = at least one emergency lighting converter has a ballast fault
= 0 = none of the ballasts have a ballast fault
= 1 = at least one normal light has a ballast fault
Number of ballast faults
Dependent on parameter
0...64 = number of individual DALI devices (ballasts or emergency lighting converters) with a fault
Group object name
Output A
Enable Group object "Number of faults statistic"
24
23
22
21
20
2
2
2
2
2
2
8
7
6
5
4
2
2
2
2
2
2
Output A
Enable Group object "No of ballast faults"
Data type
4 byte
Non DPT
19
18
17
16
2
2
2
High Byte
3
2
1
0
2
2
2
Low Byte
2
.
1 byte
DPT 5.010
Flags
C, R, T
C, R, T