ABB i-bus
KNX
Commissioning
Enable Lamp burn-in function
object "Burn-in lamps"
Options:
Linked group object:
This parameter enables the Burn-in function for a ballast or group. The function itself can be activated by
ballast or group via the ballast x/group x Burn-in lamp group object, or for all ballast/groups together via
the Output x group object Burn-in lamp/Status. This group object is enabled in the Output x Functions
parameter window. The Output x Burn-in lamps/Status group object only affects the ballasts and groups
which are set to respond to it. This property is parametrized for groups and ballasts in the A Group
x functions or A Ballast x functions parameter window.
Note
Continuous dimming of vapor filled lamps which are not burnt in can prevent the lamp from reaching its
maximum defined brightness, making the required brightness value in the area unachievable.
To guarantee maximum lamp life and correct lamp function in the dimmed state, many vapor filled
lamps must be operated for a certain number of hours at 100% brightness during initial operation before
they can be permanently dimmed.
For detailed information please see the technical data for the lamps.
Yes: The Burn-in function for the ballast/group and the Burn-in lamp group object are enabled. Burn-in
is started with the Burn-in lamp group object or the i-bus
started via the Output x Burn-in lamp/Status group object.
No: The Burn-in function for the ballast/group is not enabled.
108 2CDC507164D0201 | DG/S x.64.1.1
Yes
No
Selection of Yes option:
Dependent parameters:
Burn-in lamp
®