Parameter Selection

When a parameter selector pin is set to OFF, the corresponding set value that has been changed will be stored in the non-volatile memory. Any
data that has been previously set will be kept in the non-volatile memory regardless of whether the K3TJ is turned on or off. The following table
lists the parameters assigned to parameter selector pins 1 to 8.
OFF

Parameter Setting

The K3TJ is factory-set to display 0 when the minimum input range value is input and display 1,000 when the maximum input range value is
input.
DC Voltage Input Model
Input range
0- to 5-VDC input
1- to 5-VDC input
0- to 10-VDC input
DC Current Input Model
Input range
4 to 20 mA DC input
1. Input Range Setting
Select the 0- to 5-V, 1- to 5-V, or 0- to 10-V input range on the DC Voltage Input Model and 4- to 20-mA input range on the DC Current Input
Model.
Example: When selecting the 1- to 5-V input range on the DC Voltage Input Model
Set parameter selector pin 1 to ON, at which time the
OFF
ON
factory-set input range 0- 10 will be displayed.
1
2
3
4
5
6
7
8
Use the Up or Down Keys so that 1- 5 will be displayed.
Up Key or
Down Key
When 1- 5 is displayed, set parameter selector pin 1 to
OFF
ON
OFF to complete the input range setting.
1
2
3
4
5
6
7
8
DC Voltage Input Model
Display
0 to 5 VDC
0- 5
1- 5
1 to 5 VDC
0 to 10 VDC (factory-set)
0-10
8
ON
Display
0
0
1000
1000
to
to
Display
0
1000
to
Input range
Pin no.
1
Input range
2
Display shift
3
Scaling
4
Decimal point
5
Averaging
6
Zero limit
7
Step display
8
Display brightness
Display
1000
0
min.
Adjust the display shift and scaling for the K3TJ
while applying an actual input.
0- 10
1- 5
The input range has been changed to
the 1 to 5 V range.
DC Current Input Model
Display
4 to 20 mA DC
4-20
K3TJ
Setting
Input
max.
Input range