is set to or more when PB unit is used.
Note1)
And set
Note2) =3 to 8 is available only for inverter software version 152 or more
(VFAS1), 652 or more (VFPS1).
Note3) When PB unit is used, setting is recommended in the table below.
model
Inverter line supply (AC)
PB7-4200K
PB7-4400K
PB7-6300K
PB7-6400K
(Overvoltage limit operation) to .
380V/400V
440V
460V
480V
500V
575V
690V
16
recommended range
112% to 145%
123% to 145%
129% to 145%
134% to 145%
113% to 150%
113% to 144%
113% to 120%