8-1. Specifications

8-1. Specifications

1. General

Item
Ambient temperature
Ambient humidity
Storage temperature
Storage humidity
Vibration resistance
Shock resistance
Noise immunity
Operating environment

2. FP3 MEWNET-TR System

Item
Communication method Two - lines, half- duplex
Synchronization method
Communication path
Transmission distance
Communication speed
Input/output response
time
Controllable I/O points
Interface
Communication error
checking method

3. Performance

1) FP3 transmitter master unit
Item
Controllable I/O points*
I/O occupation points
Current consumption*
Connection method
Weight
* The total number of controllable I/O points should not be set higher than the number of I/O points of the FP3/FP10S CPU.
The total current consumption of the units used should not exceed the rated output current of their power supply unit.
See page 8 for about the limitations on unit installation.
112
0 ° C to + 55 ° C (32 ° F to 131 ° F)
30 % to 85 % RH (non - condensing)
- 20° C to + 70° C ( - 4° F to 158° F)
30 % to 85 % RH (non - condensing)
10 Hz to 55 Hz, 1 cycle/min: double amplitude of 0.75 mm (0.030 in.),
10 min on 3 axes
98 m/s
2
(10 G) or more, 4 times on 3 axes
1,000 Vp - p with pulse width, 50 ns and 1 s
(based on in - house measurements)
Must be free from corrosive gases and excessive dust.
Asynchronous system
2 - conductor cable or twisted pair cable
Max. 700 m (2,296.59 ft.) with twisted pair cable
Max. 400 m (1,312.34 ft.) with 2 - conductor cable
See page 45 for about the transmission cable.
0.5 Mbps
I/O response time is determined by the number of slave stations (FP I/O
transmitter units and expansion FP I/O terminal units).
See page 128, "8 - 5. Transfer Time," for details about the I/O response time.
Max. 128 inputs and 128 outputs/FP3 transmitter master unit
Max. 2,048 inputs and 2,048 outputs (sixteen FP3 transmitter master units)/
FP3 CPU
Max. 3,072 inputs and 3,072 outputs (twenty - four FP3 transmitter master units)/
FP10S CPU
RS485
Self - diagnosis data checking method
The controllable I/O points are selected by the operation mode selector
(selector numbers 5, 6, 7, and 8).
Input:
Select from 0, 32, 64 or 128 points.
Output: Select from 0, 32, 64 or 128 points.
The total number of input and output points that are set
130 mA or less
Terminal block (M3.5 screw)
Approx. 240 g/8.466 oz.
Description
Description
Description