Schwank 20S L Technical Manual page 28

Radiant tube heater
Hide thumbs Also See for 20S L:
Table of Contents

Advertisement

novoSchwank L
Checking adjustment
1. Turn the adjustment screw slightly to "-"
-direction. Orifice pressure must drop immediately.
If this does not happen, you must readjust the
orifice pressure until the point is reached at which
a decrease or increase in the nozzle pressure is
noticeable on the measuring instrument when the
adjustment screw is turned slightly to "+" or "-"
direction.
2. Close test nipple after the measurement!
3. Remove the measuring instrument and check if the
test nipple is gastight.
Fig. 24: Gas cock with integrated TSD
Fig. 25: Adjusting screw nozzle pressure gas combination valve
28
A
B

Advertisement

Table of Contents
loading

This manual is also suitable for:

25s l45s l55s l35s l

Table of Contents