Minimum Floor Protection
The insert must be placed on a non-combustible floor protector (cement board, sheet metal, etc.) a
minimum .018" thick (26 gauge). This floor protection must extend the full width and depth of the
enclosure and must protrude 6" in front of the door opening (18" from the enclosure opening) and the full
width of the surround panels (45" min. width).
HEARTH NOTE: If you wish to install a hearth greater than 1/2" thick, you will need to raise the insert and
enclosure height the equivalent amount. The leveling bolts may be used on the insert for adjustments.
Page 5 of 8
ZC Kit – Large Pellet Insert
Floor Protection
45" Min.
(width of surround panels)
12"
Minimum
Rear Vent Installations
Place the stove on top of the floor protection and measure the center of the
flue. This will determine the location of the wall thimble.
(99200149)
18" Min.
Enclosure Height
(measure from top of
floor protection)
Floor Protection
10/9/06
© Travis Industries, Inc.