Alarms - Danfoss EKC 316A Reference Manual

Controller for operation of evaporator on water chiller
Hide thumbs Also See for EKC 316A:
Table of Contents

Advertisement

Alarms

Symptom
All Light emitting diodes
flashing
Notes:
1) Only one alarm is displayed at a time in the controller display
and are shown in the order given above i.e. E15 will be dis-
played if S2 is not connected. If S2 is connected successfully
then the next alarm will be E17 if S3 is not connected. All alarms
are displayed in the AKM system.
2) The alarm E19 will only be active if address o10 is set to 1 or
more.
3) The alarm E17 and E18 will be only active if the Therm.Mode ad-
dress r14 is set to 1 or Reg.type address o56 is set to 3.
4) The battery alarm A44 is only active when Batt.alarm address
A34 is set to ON.
14
Possible Cause
S2 sensor cut-out.
S2 sensor short-circuited
S3 sensor cut-out
S3 sensor short-circuited
Analogue input outside range.
Pressure transmitter outside
range.
High Temperature alarm
Low Temperature alarm
No refrigerant selected
Supply to stepper motor
Battery alarm
Reference manual RS8ED102 © Danfoss 03-2006
Fault Message
Remedy
E15
Check connections at terminals 18-19 and
sensor.
E16
Check connections at terminals 18-19 and
sensor.
E17
Check connections at terminals 18-20 and
sensor.
E18
Check connections at terminals 18-20 and
sensor.
E19
E20
Check pressure transmitter, connections at
14-15 and pressure.
A1
Check cooling is effective. Check thermo-
stat relay at terminals 8-9
A2
Check ETS valve is full open and relay at
terminals 8-9
A11
Select refrigerant
A43
Check connections from EKC316A to ETS
valve.
A44
Check the battery voltage is the nominal
voltage.
EKC 316A