Danfoss EKC 316A Reference Manual page 5

Controller for operation of evaporator on water chiller
Hide thumbs Also See for EKC 316A:
Table of Contents

Advertisement

Backlash Compensation
The controller includes a procedure for compensating for
backlash on the ETS valve spindle. The parameters involved in this
procedure are listed below
Compensation value for spindle play at valve's closing point (number of steps)
Compensation value for spindle play during operation (number of steps)
Valve definition
1=Valve must open when more capacity is required (NC function)
2=Valve must close when more capacity is required (NO function)
Compensation direction
1=Compensation takes place when the valve opens (normal setting)
2=Compensation takes place when the valve closes
These parameters should not be changed and the reason the
parameters are accessible is only historical, and at some point will
be withdrawn from the menu.
EKC 316A
Reference manual RS8ED102 © Danfoss
n39
Start bcklsh (Menu=Danfoss only)
n40
Backlash (Menu=Danfoss only)
n41
Valve type (Menu=Danfoss only)
n42
Comp.dir. (Menu=Danfoss only)
03-2006
5

Advertisement

Table of Contents
loading

Table of Contents