1MRS756498 D
3.6.3.3
RED615
Application Manual
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.
By default it is expected that there is no external resistor in the
circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

Functional diagrams for control and interlocking

GUID-30FA3940-E507-4AD5-95E0-C06863113FF8 V1 EN
Figure 43:
Master Trip
The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op is connected directly to the output PO3
(X100:15-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
RED615 standard configurations
Section 3
67