5.2.10 Procedure to Enter the Transmitter Tag

1. From the My Device menu, make the following menu selections:
Shortcuts > Device Setup > Basic Setup > Device Information > Tag.
2. Click Edit. The Tag screen will be displayed.
3. Key in the tag name (for example: STT850) which can be a maximum of eight characters.
4. Click OK. The Send to Device screen will be displayed.
5. Select the Tag check box.
6. Click Send to download the change to the Transmitter, or Click Return to continue making
changes.
7.

5.2.11 Selecting the Process Variable (PV) Unit of Temperature Measurement

Engineering units affect the values of the LRV and URV. After changing the PV
engineering units to the Transmitter, verify changes to the units paramter, the LRV, and the
URV.
The Temperature measurement can be displayed in one of the pre-programmed engineering units.
1. From My Device menu, make the following menu selections:
2. Click Edit. You will be warned that if you change the value of the variable it will change the
loop current, which may upset the control process.
Revision 4.0
Shortcuts > Device Setup > Basic Setup > PV Units
STT850 Series HART/DE Option User's Manual
Page 53