Error History; Address Verification; Version; Setting The Room Temperature Detection Location - Fujitsu UTY-RVNUM Installation Manual

Hide thumbs Also See for UTY-RVNUM:
Table of Contents

Advertisement

3
Select [Function setting] with pressing the [Cursor button (Up/Down)],
and press the [Enter button].
Service
Test run
Function setting

Error history

I.U.address verification

Version

Back:
4
Select [R.C. address] of the target indoor unit with pressing the [Cur-
sor button (Up/Down)].
(R.C. Address : Remote Controller Address)
Function setting
R.C.
address
00
Cancel:
Version
5
Select the [Function No.] with pressing the [Cursor button (Left/
Right)], and select the Function No. to be set with pressing the [Cur-
sor button (Up/Down)].
Function setting
R.C.
address
00
Cancel:
Version
6
Select the [Setting No.] with pressing the [Cursor button (Left/Right)],
and select the Setting No. to be set with pressing the [Cursor button
(Up/Down)],and press the [Enter button].
Function setting
R.C.
address
00
Cancel:
Version
-Note-
"Service" screen or "Function setting" screen return to the "Submenu"
screen if there is no button operation for 1 minute.
9.3. Error history
The error history can be displayed.
Select [Error history] with the [Cursor button (Up/Down)], and press the
[Enter button].
Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back
Setting:
9.4. I.U. address verification
The refrigerant address and the indoor unit address can be displayed.
Select [I.U. address verification] with the [Cursor button (Up/Down)], and
press the [Enter button].
Service
Mo 10:00AM
Test run
Function setting
Error history
I.U.address verification
Version
Back
Setting:
Mo 10:00AM
Setting:
Mo 10:00AM
Function
Setting
No.
No.
00
00
OK:
Error history
Mo 10:00AM
Function
Setting
No.
No.
00
00
OK:
Error history
Mo 10:00AM
Function
Setting
No.
No.
00
00
OK:
Error history
Error history
[1/4 ]
Mo 10:00AM
No.
Date
Time
Address Code
1 30/07/2012 9:00AM 00
2 28/07/2012 8:00AM 00
3 13/07/2012 11:00AM 00
4 08/07/2012 1:00PM 01
Back:
Function set...
I.U. address ...
I.U. address verification
Mo 10:00AM
R.C.
Refrigerant
Indoor Unit
address
address
address
00
00
00
Back :
OK :
Error history
Version
9.5. Version
Software version of the remote controller can be displayed.
Select [Version] with the [Cursor button (Up/Down)], and press the [Enter
button].
Service
Test run
Function setting
Error history
I.U.address verification
Version
Back
Setting:
10. SETTING THE ROOM TEMPERATURE
DETECTION LOCATION
The detection location of the room temperature can be selected from the
following 2 examples. Choose the detection location that is best for the
installation location.
Refer to "9.2. Function setting".
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor.
When use this function, set "Indoor room temperature sensor switching
function (Function Number:42)" of "9.2. Function setting" to "No(00)".
B. Indoor unit/remote controller setting (room temperature sensor
selection)
The temperature sensor of the indoor unit or the remote controller can be
used to detect the room temperature.
When use this function, set "Indoor room temperature sensor switching
function (Function Number:42)" of "9.2. Function setting" to "Yes(01)".
(1)
Enable the room temperature sensor selection in function setting, which
will be described later.
(2)
Select either of the temperature sensor on the indoor unit or on the
remote controller for temperature detection. (For how to configure the
setting, refer to "5-5. R.C. sensor control" in the operating manual.)
Er 411
Er J2u
Er 156
Er 141
When select the "Remote controller setting", if the detected temperature
value between the temperature sensor of the indoor unit and the tempera-
ture sensor of the remote controller varies significantly, it is likely to return
to the control status of temperature sensor of the indoor unit temporarily.
As the temperature sensor of remote controller detects the tempera-
ture near the wall, when there is a certain difference between the room
temperature and the wall temperature, the sensor will not detect the room
temperature correctly sometimes. Especially when the outer side of the
wall on which the sensor is positioned is exposed to the open air, it is
recommended to use the temperature sensor of the indoor unit to detect
the room temperature when the indoor and outdoor temperature differ-
ence is significant.
The temperature sensor of the remote controller is not only used when
there is a problem in the detection of the temperature sensor of the indoor
unit.
Version
Mo 10:00AM
E031VXXPXXLXX
Back:
I.U. address ...
A
Indoor unit
B
Indoor unit
CAUTION
Mo 10:00AM
Function set...
En-8