Fujitsu UTY-RNRUZ2 Installation Manual

Fujitsu UTY-RNRUZ2 Installation Manual

Remote controller (wired type)
Hide thumbs Also See for UTY-RNRUZ2:

Advertisement

REMOTE CONTROLLER
(WIRED TYPE)
PART No. 9373328407
For authorized service personnel only.
Installation by endusers or not qualified persons can cause harm to
personal safety, can cause severe damage to building and product, can
lead to improper function or reduced lifetime of the equipment.

CONTENTS

1. SAFETY PRECAUTIONS . ........................................................................1
2. MAIN UNIT AND ACCESSORIES ............................................................1
3. ELECTRICAL REQUIREMENT ................................................................1
4. S ELECTING AN INSTALLATION LOCATION ..........................................2
5. I NSTALLING THE REMOTE CONTROLLER . ..........................................3
6. SETTING THE REMOTE CONTROLLER . ...............................................5
7. TEST RUN ..............................................................................................10
8. ERROR CODES .....................................................................................10
1. SAFETY PRECAUTIONS
• The "SAFETY PRECAUTIONS" indicated in the manual contain impor-
tant information pertaining to your safety. Be sure to observe them.
• For details of the operation method, refer to the operating manual.
• Request the user to keep the manual on hand for future use, such as for
relocating or repairing the unit.
Indicates a potentially or imminently hazardous situ-
ation which, if not avoided, could result in death or
WARNING
serious injury.
Installation of this product must be done by experienced service techni-
cians or professional installers only in accordance with this manual.
Installation by nonprofessional or improper installation of the product
may cause serious accidents such as injury, water leakage, electric
shock, or fire. If the product is installed in disregard of the instructions in
this manual, it will void the manufacturer's warranty.
Installation must be performed in accordance with regulations, codes,
or standards for electrical wiring and equipment in each country, region,
or the installing place.
Do not operate this unit when your hands are wet. Touching the unit with
wet hands will cause an electric shock.
When children can approach the unit or touch the unit, take preventive
measures.
Dispose of the packing materials safely. Tear and dispose of the plastic
packing bags so that children cannot play with them. There is the dan-
ger of suffocation if children play with the original plastic bags.
Indicates a potentially hazardous situation that may
CAUTION
result in minor or moderate injury or damage to
property.
When detecting the room temperature using the remote controller,
please set up the remote controller according to the following conditions.
If the remote controller is not well set, the correct room temperature will
not be detected, and thus the abnormal conditions like "not cool" or "not
heat" will occur even if the air-conditioner is running normally. :
• A location with an average temperature for the room being air condi-
tioned.
• Locate where is not be affected by inflow of outside air such as caused
by opening and closing a door.
• Not directly exposed to the outlet air from the air conditioner.
• Out of direct sunlight.
• Away from the influence of other heat sources.
Do not install the unit in the following areas:
• Do not install the unit near a source of heat, steam, or flammable gas.
Otherwise, fire could result.
• Area filled with mineral oil or containing a large amount of splashed oil
or steam, such as a kitchen. It will deteriorate plastic parts, causing the
parts to fall.
• Area containing equipment that generates electromagnetic interfer-
ence. It will cause the control system to malfunction, and cause er-
roneous operation.
• Install the unit in a well-ventilated place avoiding rains and direct sun-
light.
Do not touch the switches with sharp objects. Doing so will cause injury,
trouble, or electric shock.
Do not expose this unit directly to water. Doing so will cause trouble,
electric shock, or heating.
Do not set vessels containing a liquid on this unit. Doing so will cause
heating, fire, or electric shock.
2. MAIN UNIT AND ACCESSORIES
The following installation parts are supplied. Use them as required.
Name and shape
Q'ty
Wired remote controller
1
Installation manual
(This manual)
1
Operating manual
1
3. ELECTRICAL REQUIREMENT
When connecting the remote controller use the following wiring.
Cable size
Wire type
22 to 16 AWG
Non polar
(0.33 to 1.25 mm²)
Thermostat cable
18AWG
Select a flexible cable that can be bound using cable ties from over the
cable sheath inside this unit.
Maximum connectable number of remote controllers by cable size and the
length.
Cable size
(L* ≤ 100 m)
AWG
mm²
VRF
16
1.25
18
0.75 (1.25 > S* ≥ 0.75)
20
0.5 (0.75 > S* ≥ 0.5)
22
0.3 (0.5 > S* ≥ 0.3)
*L: Total cable length, *S: Cable size
Name and shape
CD-ROM
Screw (M4 × 16mm)
For installing the remote
controller
Cable tie
For remote controller and
remote controller cable
binding
Remarks
Use sheathed
2 core
twisted pair cable
Use sheathed non
2 core
twisted pair cable
Max. connectable number of
remote controllers
328 ft < L*
820 ft < L*
L* ≤ 328 ft
≤ 820 ft
≤ 1,640 ft
(101 m < L*
(251 m < L*
≤ 250 m)
≤ 500 m)
RAC
VRF
RAC
VRF
4
2
4
2
4
4
2
4
2
2
4
2
2
2
2
4
2
1
1
1
Q'ty
1
2
1
RAC
2
2
2
1
En-1

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu UTY-RNRUZ2

  • Page 1: Remote Controller

    REMOTE CONTROLLER Do not install the unit in the following areas: • Do not install the unit near a source of heat, steam, or flammable gas. (WIRED TYPE) Otherwise, fire could result. INSTALLATION MANUAL • Area filled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to fall. • Area containing equipment that generates electromagnetic interfer- ence. It will cause the control system to malfunction, and cause er- PART No. 9373328407 roneous operation. For authorized service personnel only. • Install the unit in a well-ventilated place avoiding rains and direct sun- light. Installation by endusers or not qualified persons can cause harm to personal safety, can cause severe damage to building and product, can Do not touch the switches with sharp objects. Doing so will cause injury, lead to improper function or reduced lifetime of the equipment. trouble, or electric shock. Do not expose this unit directly to water. Doing so will cause trouble, electric shock, or heating. CONTENTS Do not set vessels containing a liquid on this unit. Doing so will cause 1. SAFETY PRECAUTIONS .................1 heating, fire, or electric shock. 2. MAIN UNIT AND ACCESSORIES ............1 3. ELECTRICAL REQUIREMENT ..............1 4. S ELECTING AN INSTALLATION LOCATION ..........2 2.
  • Page 2: No

    “Away”. (n) Status icons: Refer to operating manual. For the screen display other than Chinese, this product uses a Bitmap font made and developed by Ricoh Company, Ltd. 4.2. S etting the room temperature detection location Hole: 1/4 × 3/16 Hole: 1/2 × 3/16 (a) (b) (c) (d) (6 × 4.5) (12.5 × 4.5) CAUTION (a) Room temperature sensor (inside) As the temperature sensor of remote controller detects the temperature All Fujitsu General products are near the wall, when there is a certain difference between the room (b) Operation (Ocupied/Unoccupied) manufactured to metric units temperature and the wall temperature, the sensor will not detect the button: and tolerances. United States room temperature correctly sometimes. Especially when the outer side It is possible to operate only while customary units are provided for of the wall on which the sensor is positioned is exposed to the open air, displaying the Monitor Mode reference only. it is recommended to use the temperature sensor of the indoor unit to screen. In cases where exact...
  • Page 3: I Nstalling The Remote Controller

    5.1.2. Group control 5. I NSTALLING THE REMOTE With a single remote controller, up to 16 units can be simultaneously oper- CONTROLLER ated. Indoor unit 0 Indoor unit 1 Indoor unit 2 Indoor unit 3 WARNING Always use the accessories and specified installation work parts. Check the state of the installation parts. Not using the specified parts will cause units to fall off, water leakage, electric shock, fire, etc. Install at a place that can withstand the weight of the unit and install firmly so that the unit will not topple or fall. Remote controller When installing this unit, make sure that there are no children nearby. Otherwise, injury or electric shock could result. 5.1.3. Multiple remote control Before starting installation work, turn off the power of this unit and the connection destination. Do not turn on the power again until installation Number of connectable remote controllers. VRF: 4, RAC: 2 is completed. Otherwise, it will cause electric shock or fire. Multiple installation method described above is prohibited to combine 3 Use the accessories or specified connection cables. Do not modify con- Wired type with 2 Wired Type. nection cables other than those specified, do not use extension cords, In multiple installations, the following functions are restricted. and do not use independent branch wiring. The allowable current will be Functions that can only be used with a Master Remote Controller: exceeded and cause electric shock or fire. • Auto Off Timer Setting *1 Install the remote controller cables securely to the terminal block. Con- • Weekly Timer Setting *1 firm that external force is not applied to the cable. Use remote controller • Set Temp. Auto Return *1 cables made of the specified wire. If intermediate connection or inser- • 6.3.11 Optimum Start Setting...
  • Page 4 5.2.3. Setting the DIP switch 5.3.2. Connecting the remote controller cable CAUTION CAUTION Use an insulated screwdriver to set the DIP switches. Do not touch the When connecting a remote controller cable to the remote controller DIP switch with your hands. terminal block, please use the specified torque to tighten screws. If you over-tighten screws, they will break the terminal unit. Front case (back side) Be careful to avoid breaking the cable by over-tightening the cable tie. Tightening torque 7.1 to 10.6 lbf•in (0.8 to 1.2 N•m) Set the DIP switch to ON Fasten the outside covering of the connection cable with the cable tie. Tighten the cable tie firmly so that pulling force does not propagate to the terminal connection even if force of 30 N is applied to the cable. OFF ON Select a flexible cable that can be bound using cable ties from over the cable sheath inside this unit. Before using this product, always set DIP switch to “ON”. If not set, when the main power is turned on again, the set data by menu operation will be erased and cause erroneous operation. Cable tie [DIP Switch] • Performs the enabling/disabling of the backup function by the internal battery. • It is disabled when shipped from the factory to prevent consumption of the charge. PROHIBITED GOOD 5.3. Installation CAUTION Perform wiring so that water does not enter this unit along the external 5.3.3. Attach the front case wiring. Always install a trap to the wiring or take other countermeasures.
  • Page 5: Test Run

    6.4.1. Error History ..........8 6.4.2. Setting Status List ........8 Set to "2WIRE" the 6.4.3. Filter Sign Reset* ........8 DIP switch (SW1) Indoor unit 6.4.4. Version ............9 PC board 6.4.5. Test Run ............. 9 Other Settings 6.4.6. R.C. Address Setting........9 6.4.7. I.U. Address Verification ......9 6.4.8. Function Setting ......... 9 Remote controller Connector CNC01 cable (Non-polar) Connecting cable 6.4.9. Installer Password Change ...... 10 (onboard) 6.4.10. Initialization ..........
  • Page 6: Displayed

    Touch [ ] or [ ] to set hours, minutes, and AM/PM. Touch [OK] to The “Initial Setting” screen has three pages. Touch [Next Page] or [Previous Page] to switch between screens. Touch the items you return to the “Date and Time Setting” screen. wish to configure. Touch [OK] on the “Date and Time Setting” screen to display the (Items that indoor unit does not support are not displayed.) “Temp. Unit Setting” screen. Initial Setting Page 1/ 3 Initial Setting Initial Setting Page 2/ 3 Page 3/ 3 R.C. Sensor Master Indoor RC Master/ Language Setting Date Setting Deadband Setting Setting Unit Setting Slave Setting Time Date and Time Setting...
  • Page 7 6.3.4. R.C. Group Name Setting 6.3.7. Password Setting (administrator password) Touch the [R.C. Group Name Setting] on the “Initial Setting” screen. The Set or change the administrator password. “R.C. Group Name Setting” screen is displayed. Touch the [Password Setting] on the “Initial Setting” screen. The “Password Setting” screen is displayed. • About the “R.C. Group Name Setting” screen Then touch the [Change Password] on the “Password Setting” screen. The “Change Password” screen is displayed. Touch the relevant key and enter a R.C.Group Name Setting Enter the current password, then touch the [OK]. name. Touch [OK] to return to the ABCDEFGHIJKLM│ Over The default password is “0000” (4 digits). “Initial Setting” screen after dis- playing the “Confirmation screen”. Enter the new password, then touch the [OK]. It returns to the Fixed 0–9 “Password Setting” screen. _– Phrase Cancel Change Password Password Setting Password Verification Enter Current Password Enter New Password (a) Input area: If the number of input characters exceeds that permitted, Change Password “Over” will be displayed on the right side.
  • Page 8: Initialization

    • Room Temp. The address selection screen is displayed. Select the address of the indoor unit you want to match to the display number selected at Set to “Visible” to display the room temperature detected by this unit on step 2 with [ ] or [ the monitor screen. When [OK] is touched, the display returns to the screen of 2 and Touch the [Room Temp.] on the “Display Item Setting” screen. The the address is interchanged with the selected display number (Unit “Room Temp.” screen is displayed. X). Repeat steps 2 and 3 up to the desired order. Touch [OK] after touching [Visible] or [Invisible] to return to the When [Back] of the screen of 2 is touched, the display returns to the “Display Item Setting” screen. “Initial Setting” screen. Touch the [OK] on the “Display Item Setting”. It returns to the “Initial Setting” screen. I.U. Display Number Setting I.U. Display Number Setting Page 1/ 6 Page 1/ 4 Disp No. System–Unit / Ref.–In. Disp No. System–Unit / Ref.–In. Unit 1 002–01 01–01...
  • Page 9: Test Run

    6.4.4. Version 6.4.7. I.U. Address Verification Check the address and position of the indoor unit. Touch the [Version] on the “Maintenance” Version screen. The “Version” screen is displayed. Touch the [I.U. Address Verification] on the “Maintenance” screen. Touch [Back] to return to the “Maintenance” E000V00P00L00 The “I.U. Address Verification” screen is displayed. screen. If there are multiple pages, you can switch between them by touch- ing [Next Page] or [Previous Page]. Back Touch [Check] to display the indoor unit address checking start screen. 6.4.5. Test Run Touch [Yes] to display the confirmation screen. Carry out a test run after completing configuration. Select the indoor unit to be checked. If there are multiple pages, you can switch between them by touching [Next Page] or [Previ- Touch the [Test Run] on the “Maintenance” Test Run ous Page]. The selected indoor unit will start to blow air and flash a screen. The “Test Run” screen is dis- LED*. (*Only when the indoor unit has the relevant functions) played. The test run will be performed. OK? Touch [Back] on the confirmation screen to return to the previous Touch [OK] to return to the “Maintenance” screen.
  • Page 10: Touch The [Next Page] (Or [Previous Page]) To Switch To Other Con

    6.4.9. Installer Password Change Change the Installer password. Touch the [Installer Password Change] on the “Maintenance” screen. The “Installer Password Verification” screen is displayed. Enter the current password, then touch the [OK]. The default password is “0000” (4 digits). The “Installer Password Change” screen is displayed. Enter the new password, then touch the [OK]. It returns to the “Maintenance” screen. Installer Password Verification Installer Password Change Enter Current Password Enter New Password Cancel Cancel 6.4.10. Initialization Require an Installer password. Touch the [Initialization] on the “Main- Initialization tenance” screen. Enter the Installer password. The “Initialization” screen is Remote controller will be initialized to the factory default setting. OK? displayed.