4. Maintenance and Service

D Trained personnel should perform a visual and physical test according Table 6 as recommended by
NFPA-72 (National Fire Alarm Code).
D For cleaning the detector surface, use a common window cleaner and a soft, clean cloth.
Notify all concerned parties before any maintenance or testing of the fire alarm sy­
stem, and after completion of these activities.
Note:
D The FCP-500-C and FCP-500-C-P must be replaced every five years. The chemical (CO) sensor turns off
at five years of operation. The LED double-flashes every 8 to 12 sec, indicating trouble, and the detector
continues to function as an optical (O) detector.
Table 6: Testing Detector
Test Steps
1
Check the LED (see Table 7)
2
Check the detector's mounting
Visually check for damage or contamination of the detector sur­
3
face
Check the area for factors (such as lightening) that could inhi­
4
bit the detector's performance
5
Perform Electronic Functional Test (see Section 6.)
6
Perform Sensitivity Test (see Section 7.)
7
Test the optical sensor (see Section 8.)
8
Test the optical sensor and the CO sensor (see Section 9.)
Table 7: LED Operation
Status
Normal
Alarm
Trouble
Test mode

5. Dry Reed Contact

1. Place the test tool with the FAA-500-TTL test adap­
ter with magnet up against the detector head.
2. Turn the test tool until the magnet activates the
dry reed contact (see Fig. 9.). Normally the green
LED flashes once every 8 to 12 sec. When the dry
reed contact activates, the LED flashes once every
second.

6. Electronic Functional Test

1. Activate the dry reed contact (Section 5, Dry Reed
Contact).
2. Leave the magnet on the test tool by the dry reed
contact for 10 sec. Count 10 flashes of the LED.
The detector activates a test alarm and the LED
turns red.
BDL-F01U000626 | A7 | 2007.07
LED
green, flashes every 8 sec
red, steady
green, double flash every 8 to12 sec
green, flashes once every second
Available from A1 Security Cameras
www.a1securitycameras.com email: sales@a1securitycameras.com
Detector Type
FCP-500
FCP-500-P
X
X
X
X
X
X
X
-
CO sensor
(only FCP-500-C
detectors)
LED
FCP-500 Series
FCP-500-C
FCP-500-C-P
X
X
X
X
X
X
X
X
Dry reed
contact