FCP-500 Series

1. Specifications

Table 1: Models
Type
Description
FCP-500-C
Photoelectric Detector with Carbon Monoxide Detection,
Color White
FCP-500-C-P
Photoelectric Detector with Carbon Monoxide Detection,
Transparent with Color Inserts
FCP-500
Photoelectric Detector, Color White
FCP-500-P
Photoelectric Detector, Transparent with Color Inserts
The CO sensor has not been evaluated to the requirements of UL 2075 or for its ability to
detect a fire.
The FCP-500-C and FCP-500-C-P detect CO as a component of a fire.
Do not use the FCP-500-C and FCP-500-C-P as CO detectors.
Table 2: Options (included)
Type
Description
FAA-500-BB-UL
Ceiling Mount Back Box for US
FCA-500
Four-Wire Base (six conductors)
FCA-500-E
Four-Wire EOL Base (six conductors)
FAA-500-TR-W
Trim Ring, White
FAA-500-TR-P
Trim Ring, Transparent with Color Inserts
Table 3: Options (optional)
Type
Description
DRA-5
Remote LED Annunciator
FAA-500-TTL
Test Adapter with Magnet
FAA-500-RTL
Removal Tool
Table 4: Technical Data
Operating Voltage
Current Consumption
- FCA-500 / FCA-500 with DRA-5
- FCA-500-E / FCA-500-E with DRA-5
Alarm Output
Remote LED Output
Rating of Trouble/Alarm Relay
Reset Time
Max. Start-up Time
Sensitivity
Mounting Locations
Maximum Mounting Height
Minimum Mounting Height
Bosch Security Systems
Available from A1 Security Cameras
www.a1securitycameras.com email: sales@a1securitycameras.com
9.7 V DC to 30 V DC
Standby
3 mA / 3 mA
24 mA / 24 mA
Alarm resistance 680 Ω or 0 Ω (US only)
Maximum 20 mA
1 A @ 30 V DC
The detector resets if power is interrupted for at
least 2 sec.
22 sec
1.3 ...2.9 %/ft (4.3 ... 9.5 %/m)
Refer to NFPA-72 guidelines.
Refer to NFPA-72 guidelines.
9.0 ft (2,7 m)
BDL-F01U000626 | A7 | 2007.07
1
Material No.
4.998.150.703
4.998.150.705
4.998.150.702
4.998.150.704
Material No.
F.01U.510.767
4.998.151.300
4.998.151.301
4.998.151.295
4.998.151.296
Material No.
-
F.01U.508.725
F.01U.508.720
Alarm/Trouble
47 mA / 52 mA
47 mA / 58 mA