11 TROUBLESHOOTING
11.4.2 End codes (Complete codes) returned to an external device during data
communication
End code
00
• Normal completion
H
• Codes for command/response type of subheader are not within the
specifications.
Communication using fixed buffer
50
H
Communication using MC protocol
• In communication using the fixed buffer, if the data length setting is less than
the actual data count, the remaining data is determined as the second data and
processed. In this case, a subheader undefined command type error may
occur.
• When "ASCII code communication" is selected (BFM #24b1: ON) in the
[Communication data code settings] of operational settings parameters of FA
54
H
Configurator-EN, ASCII code data that cannot be converted to binary code was
received from an external device.
56
• Device designation from an external side is incorrect.
H
• The number of points for a command designated by an external device
exceeds the maximum number of processing points for each processing
(number of processes that can be executed per communication).
• Head device number to the designated points exceeds the maximum
addresses (device number).
• When performing batch read/write operations on C200 to C255, the address
57
H
(device numbers), which was designated with the odd number of points, is
exceeded.
• Byte length of a command does not conform to the specifications.
• When writing data, the set number of data points written is different from the
value of the designated number.
• Head device number of a command designated by an external device is set
outside the range that can be designated.
58
H
• A word device is designated in a command for bit devices.
• The head number of bit devices is designated by a value other than a multiple
of 16 in a command for word devices.
• The PLC and the Ethernet module cannot communicate.
5B
H
• The PLC cannot process requests from an external device.
• Communication time between the Ethernet module and the PLC exceeded PLC
60
H
monitoring timer value.
Fixed
: Fixed buffer communication
11 - 19
This section explains the end codes (complete codes) that are added to responses
when communicating using the fixed buffer or the MC protocol.
For more details on the error codes that are added to responses during communication
using A compatible 1E frames through the MC protocol, see Section 11.4.3.
For more details on the end codes (error codes) that are stored in the buffer memory of
the Ethernet module, see Section 11.4.4.
Description
Communication processing
MC
: Communication using MC protocol
Processing
• Check and correct
command/response type set by
Command/
an external device.
response type
(The Ethernet module
automatically adds
60
H
command/response type; the
00
to 05
H
H
user does not need to set
13
to 16
H
H
these.)
See NOTE in Section 11.4.4.
• Check and correct the data
length.
• Check and correct the send
data of the external device.
• Correct the device designated.
• Correct the designated points or
device number.
• Check the data length of the
command and redo the data
setting.
• Designate the appropriate
values within the range that are
allowed for each processing.
• Correct the command or the
designated device.
• Fix the faulty parts by referring
to the abnormal codes
appended to the end codes
(see Section 11.4.3).
• Increase the monitoring timer
value.
MELSEC-F
Communication function
Fixed
MC
11 - 19