18 | Water side pressure drop
PSC Motor
Electrical Data Table - PSC Blower Motor
VOLTAGE
RATED
CODE
VOLTAGE
MODELS
0
115/1/60
009
1
208-230/1/60
2
265-277/1/60
0
115/1/60
012
1
208-230/1/60
2
265-277/1/60
0
115/1/60
015
1
208-230/1/60
2
265-277/1/60
1
208-230/1/60
018
2
265-277/1/60
* These values are reported at 167°F (75°C), not room temperature. All other resistance values must be measured with
compressor at room temperature. Resistance value tolerance +/- 7%.
WATER SIDE PRESSURE DROP
Model
GPM
Pressure Drop (PSIG)
1.3
1.5
009
2.0
2.5
3.0
1.5
2.0
012
2.5
3.0
4.0
2.5
3.0
015
3.5
4.0
5.0
2.5
3.0
018
4.0
5.0
6.0
8733942456 (2016/04)
COMPRESSOR
QTY
RLA
LRA
VOLTAGE
MIN/MAX
104/126
1
7.0
45.6
197/253
1
3.4
22.2
239/291
1
2.9
18.8
104/126
1
9.6
58.4
197/253
1
4.6
27.9
239/291
1
3.8
22.2
104/126
1
12.7
63.0
197/253
1
5.6
29.0
239/291
1
4.6
20.0
197/253
1
7.4
33.0
239/291
1
6.0
28.0
Pressure Drop (ft of H2O)
0.98
1.26
2.11
3.16
4.39
1.26
2.11
3.16
4.39
7.36
1.08
1.50
1.98
2.52
3.77
1.08
1.50
2.52
3.77
5.24
Subject to change without prior notice
TOTAL UNIT PSC MOTOR
FLA
MIN
MAX
CIRCUIT
FUSE/
AMPS
HACR
2.1
10.9
15
0.9
5.2
15
0.7
4.3
15
1.3
13.3
25
0.8
6.6
15
0.8
5.6
15
1.3
17.2
25
0.8
7.8
15
0.8
6.6
15
0.8
10.1
15
0.8
8.3
15
2.25
2.91
4.87
7.29
10.13
2.91
4.87
7.29
10.1
17.0
2.50
3.47
4.58
5.82
8.70
2.50
3.47
5.82
8.70
12.1
CA Model
COMPRESSOR SERVICE
COLD WINDING
RUN
RESISTANCE (Ω)
CAPACITO
R (μF/V)
SINGLE
SINGLE
PHASE:
PHASE:
S-C
R-C
3.48
0.71
35/240
7.35
2.95
15/370
10.74
4.27
10/440
3.15
0.58
35/370
5.90
2.30
20/370
8.70
3.47
15/440
N/A
N/A
40/370
5.45
2.31
25/440
7.39
3.58
15/440
3.05*
2.41*
35/370
2.57*
3.26*
35/440
CA Model