ICP DAS USA M-4132 User Manual page 13

Hide thumbs Also See for M-4132:
Table of Contents

Advertisement

Table 6: Dip switch and trigger button for initial function
Option
Recover default
setting forever
IP recover default
setting for this
time
IP recover default
setting forever
Display the
current IP and
version
Normal setting
M-4132 User Manual (Version 1.60, May/2014)
Figure 8: Dip Switch and Trigger Button
State
SW2=ON
SW1=ON
To press the TB about 40
second after power on
SW2= OFF
SW1= ON
To press the TB about 40
second after power on
SW2= ON
SW1= OFF
To press the TB about 40
second after power on
SW2=OFF
SW1=OFF
To press the TB about 40
second after power on
The other states
Description
All system settings will be cleared and
recover default settings.
(Warning: it will not restore settings
after clear)
After power on, it will set IP to default
setting (192.168.1.217) for this time,
but it will restore original IP at next
time.
After power on, it will set IP to default
setting (192.168.1.217) and save to
flash.
After power on, it will display the
message about current IP and version
information from Com Port(RS-232).
Normal state; It will not change any
setting and data.