ok
C1
C2
Activating manual control
Briefly press both buttons simultaneously
¾
Activating permanent switching
Press both buttons simultaneously for 2 seconds
¾
Cancelling manual/permanent switching
Press both buttons simultaneously
¾

Hour counter

The operating hours of the channel (relay) are displayed and
deleted in the OPTIONS menu. If the number of operating
hours exceeds the value set in the Service menu, SERVICE will
appear in the display.
Example: Replace a lamp after after 5,000 h.
Delete operating hours or set a higher value in Service (e.g.
¾
to 10,000 h)
Time signal can be received with appropriate top2
RC antenna (only with SELEKTA 171 top2 RC)
L The top2 RC-DCF antenna (9070410) and the top2
RC-GPS antenna (9070610) can be connected to the
SELEKTA 171 top2 RC time switch.
L Follow the advice in the top2 RC-DCF/GPS antenna opera-
ting instructions.
L Connection to the top2 RC-DCF antenna allows the time
switch to be automatically synchronised via DCF signal.
L After connecting to the power supply or resetting, the
automatic display is changed to as soon as the DCF trans-
mission signal has been received.
L Additional power unit (9070892) required for GPS if only
one device is connected to the antenna.
Adjusting of time zones
After successful synchronisation, the time zone can be altered
in the TIME/DATE menu option.
In the TIME menu (display: ALTER HOUR) correct the appli-
¾
cable local time (time zone).
DCF transmission signal
reception:
Display: Day + Month + RC
(Radio Control)
No reception of the DCF
transmission signal
Display: e.g. 24 11 07
No connection to antenna:
Display: e.g. 24 11 07
Ext1
L
N
DATA
+
0
6
12
18
24
MENU
OK
max.100 m
1
2
0,5mm -
2
2,5mm
230-240V~
50-60Hz
16(10)A 250V~
R 10a -30T
C1
1
2
3
Using the OBELISK top2 memory card
L The OBELISK top2 memory card is not included in the
scope of supply of the device, but can be ordered as an
accessory (9070404).
All functions can also be set on the PC using the OBELISK
software and transferred to the device via the memory card.
Insert memory card in the time switch
¾
Read in/out saved switching times and device setups in
¾
the time switch or start Obelisk program
Remove memory card after copying etc.
¾
!
Avoid mechanical overload and contamination during
storage/transport
Copying OBELISK → Time switch
This copies the switching programme and optionally all time
switch settings (e.g. form time etc.) from the memory card to
the time switch.
Copying Time switch → OBELISK
Copies all switching programmes and settings from the
time switch to the memory card.
Starting OBELISK program
Takes over the switching times that are programmed on the
memory card.
As soon as the memory card is removed, the switching times
of the time switch are re-activated.
OBELISK
u
COPY
COPY TIME
OBELISK ->
SWITCH ->
TIME
OBELISK
OVERWRITE
OVERWRITE
OK
OK
L The current OBELISK top2 PC software are available at
www.theben.de

Resetting the time switch

Press the 4 buttons simultaneously
¾
▻ You can choose between RETAIN PROGRAM and DELETE
PROGRAM
u
u
RUN OBELISK
CHECK
OBELISK
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1710100Selekta 172 top21720100

Table of Contents