  • Page 1 Prolon Control Systems Lonbox PSW5000 Users Manual Switch interface for building automation Prolon Control Systems 9/25/2014...
  • Page 2: Table Of Contents

    Prolon Control Systems Index Index ............................... 2 Overview ............................3 Configuration ..........................3 Functional Blocks ..........................6 Node Object ..........................6 Network Variables ........................6 Configuration Properties ......................6 Switch ............................7 Network Variables ........................7 Configuration Properties ......................7 Scene Panel ..........................
  • Page 3: Overview

    Prolon Control Systems Overview The interface series PSW50xx is designed to be used in LonWorks based systems. The devices are used as an interface between one or more physical switches and a building automation installation. The normal function of the interface is to allow for manual operation of lights, sun blinds, ventilation etc.
  • Page 4 Prolon Control Systems The following table documents the different configuration modes that a digital input can be used in. SWA_ACTIVE_ON Used for toggle switch types When input is active the configured on level is transmitted. When input is passive OFF = 0% 0 is transmitted...
  • Page 5 Prolon Control Systems configured in on level and a rotation of 0 (zero) SWA_SETTING_UP If clicked sends a SET_UP with a level of 100%. When held sends SET_UP with a setting level as configured in on level and a rotation of 0 (zero). When released after being held sends SET_STOP.
  • Page 6: Functional Blocks

    Prolon Control Systems Functional Blocks Node Object “Node” Function block name: LonMark object type: Number of blocks in device: Principal network variable: nvoStatus (SNVT_obj_status) Network Variables nviRequest LonMark network variable type name: SNVT_obj_request LonMark network variable type id: nvoStatus LonMark network variable type name:...
  • Page 7: Switch

    Prolon Control Systems Switch “Switch” Function block name: LonMark object type: 3200 LonMark object name: SFPTswitch Number of blocks in device: Principal network variable: nvoSwitch (SNVT_switch) The switch function reflects the state of one or more connected switch button. Using the node object digital inputs can be assigned to the Switch function and the functionality can be configured.
  • Page 8: Scene Panel

    Prolon Control Systems Maximum Ouput LonMark configuration property type: LonMark configuration property name: SCPTmaxOut Applies to: Function block Default value: 100.0 % Maximum Send Time LonMark configuration property type: LonMark configuration property name: UCPTturnOnLevel Applies to: Function block Default value: 100.0 %.
  • Page 9: Network Variables

    Prolon Control Systems Network Variables nviScene LonMark network variable type name: SNVT_scene LonMark network variable type id: nvoSceneValue LonMark network variable type name: SNVT_switch LonMark network variable type id: nviSetting LonMark network variable type name: SNVT_setting LonMark network variable type id:...
  • Page 10: Switch Connection Information

    Prolon Control Systems Switch Connection Information The following figures show the wire information for the different models available. Mounting Instruction The interface device is designed to be build directly together with a low voltage switch and LED indicator module. The input wires must not be extedended and the inputs and outputs should only be connected to switches or LED’s as shown below.
  • Page 11 Prolon Control Systems Svagstrømstryk TP/FT-10 DI 1 DI 2 24 V d.c. DI 3 DI 4 PSW5036 DI 5 DI 6 DO 1 DO 2 DO 3 Figur 4 Lonbox PSW5036 - 6 indgange, 3 udgange Svagstrømstryk TP/FT-10 DI 1 DI 2 24 V d.c.
  • Page 12: Technical Data

    Prolon Control Systems Technical Data Interface LonWorks 2.0 TP/FT-10 (bus eller fri) Processor type FT5000 Forsyning 24 V d.c. Forbrug Norm 15 mA @ 24 V d.c. Max. 25 mA @ 24 V d.c. (uden udgange) Størrelse 32 * 35 * 15 mm...