Overview; Configuration - Prolon Lonbox PSW5000 User Manual

Table of Contents

Advertisement

Prolon Control Systems

Overview

The interface series PSW50xx is designed to be used in LonWorks based systems. The devices
are used as an interface between one or more physical switches and a building automation
installation. The normal function of the interface is to allow for manual operation of lights, sun
blinds, ventilation etc.
The inputs can be assigned to operate the build-in LonMark Switch objects. It is possible to use 4
inputs to operate 4 separate light groups or to use all 4 inputs to operate one single light group with
different functions.
The series consists of 5 models with different I / O configuration, the number of I / O in the various
models is especially adapted to suit standard FUGA and OPUS switches.
The interfaces device uses LonWorks 2.0 technology.
Software functions are according to the current LonMark standard, inputs control Switch 3200 or
Scene Panel 3250. In addition scenes can be configured with the build-in Scene Controllers.
The device is very compact and designed to be placed behind the switch module when mounted in
or on a wall.
In addition to the wires for connecting switches and indicators, the PSW50XX device has two wires
for TP/FT-10 network communication and two wires for connection of an external 24Vdc power
supply, normally these two pairs are connected to a network cable. Only the communication and
power wires should be run away from the device. The PSW50XX device should be combined with
the switch interface into one unit; I/O is not designed to be wired away from the device.
It is possible to transmit the service pin message by activating inputs 1 and 2 simultaneously.

Configuration

The main configuration of the function of the interface is done through two configuration properties
on the Node Object. The configuration is located on the Node Object because the configuration
applies to the physical digital inputs and not the other function block (switch).
Using the node object UCPTdiAssignment each digital input is told which switch function block to
apply its operation to. This means that for a 4 input module, the 4 inputs can operate 4 individual
switch function blocks or all 4 digital inputs can be assigned to apply different actions to the same
one switch function block.
In default configuration each input operates one function block.
To change so that for example input 1 and 2 operates Switch[0] and inputs 3 and 4 operates
Switch[1] set UCPTdiAssignment to 0,0,1,1.
When the 4 digital inputs has been assigned to a switch functional block, the operation or action
that the digital input will have is selected through the SCPTdiSwitchAction configuration property.
Initially each digital input will work in the mode SWA_DIM_UP_DOWN_OFF_ON_LEVEL.
Lonbox PSW5000
Users Manual
Page 3