Prolon Control Systems
The following table documents the different configuration modes that a digital input can be used in.
SWA_ACTIVE_ON
SWA_ACTIVE_OFF
SWA_ON_LEVEL
SWA_ON_LAST
SWA_OFF
SWA_AUTO
SWA_DIM_UP
SWA_DIM_DOWN
SWA_DIM_UP_ON_LEVEL
SWA_DIM_UP_ON_LAST
SWA_DIM_DOWN_OFF
SWA_DIM_UP_DOWN_OFF_ON_LEVEL
SWA_DIM_UP_DOWN_OFF_ON_LAST
SWA_TOGGLE
SWA_SETTING_ON
SWA_SETTING_OFF
Lonbox PSW5000
Used for toggle switch types
When input is active the configured on level is transmitted.
When input is passive OFF = 0% 0 is transmitted
Used for toggle switch types
When input is active OFF = 0% 0 is transmitted.
When input is passive, the configured on level is transmitted.
When activated the configured on level is transmitted.
When activated, the last known on level is transmitted.
When activated, OFF 0% 0 is transmitted
When activated an invalid switch value is transmitted 127.5% -1,
this is used to reset manual override of a light controller.
When pressed and as long as the switch is held active the
switch level is dimmed up using configured step value.
When pressed and as long as the switch is held active the
switch level is dimmed down using configured step value.
If clicked configured on level is transmitted.
If held active the switch level is dimmed up using configured
step value.
If clicked the last known on level is transmitted.
If held active the switch level is dimmed up using configured
step value.
If clicked, OFF 0% 0 is transmitted
If held active the switch level is dimmed down using configured
step value.
If clicked either OFF 0% 0 or configured on level is transmitted.
If held active the switch level is dimmed up or down using
configured step value.
If clicked either OFF 0% 0 or last known on level is transmitted.
If held active the switch level is dimmed up or down using
configured step value.
Toggles the switch level transmitted between off and configured
on level.
When activated sends SET_ON with a setting level as
configured in on level and a rotation of 0 (zero)
When activated sends SET_OFF with a setting level as
Users Manual