3.2.
3.2.1.
3.3.
3.3.1.
22
COM600 series 5.0
Slave Protocols (Ethernet) and Applications Technical Refer-
ence Manual
Services
T3
supported TimeStamp resol-
ution
c6 – shall declare support for at least one (BRCB or URCB).
c7 – shall declare support for at least one (QueryLogByTime or QueryLogByEntry).
c8 – shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage).
c9 – shall declare support if TP association is available.
c10 – shall declare support for at least one (SendMSVMessage or SendUSVMessage).

SCL conformance

SCL conformance statement

The SCL conformance statement defines several degrees of conformance for which
implementations may declare support of the substation configuration language. [1]
Table 3.2.1-1 SCL conformance degrees
SCL Conformance
SCL.1
SCL File for Imple-
mentation Available
(offline)
SCL.2
SCL File available
from implementation
online
SCL.3
SCL implementation
reconfiguration sup-
ported online

PICS - protocol conformance statement

Profile conformance

Table 3.3.1-1 and Table 3.3.1-2 define the basic conformance statement.
AA:
Client/Sub-
TP/MC
scriber
Client-
CR
Base
F/S
Value/Range
O
O
O
O
1MRS758692
Server/Pub-
Value/Comments
lisher
T5
(nearest negative
power of 2 in
seconds)
Server-
CR
Base
F/S
Value/Range
M
M
SUPPOR-
TED
O
O
-
O
O
-