Siemens Simatic ET200pro Operating Instruction page 94

Cpu 1516pro-2 pn
Hide thumbs Also See for Simatic ET200pro:
Table of Contents

Advertisement

SIMATIC memory card
8.1 SIMATIC memory card - overview
Table 8- 2
File type
S7_JOB.S7S
SIMATIC.HMI\Backup\*.psb
SIMATICHMI_Backups_DMS.bin
__LOG__
crdinfo.bin
DUMP.S7S
*.pdf, *.txt, *.csv, ....
Use the serial number for copy protection
You can set up copy protection for CPUs which binds execution of the block to a specific
SIMATIC memory card. Configuration is carried out in STEP 7 in the properties of the block
"Bind to serial number of the SIMATIC memory card".
You can only execute the block if it is on the SIMATIC memory card with the specified serial
number (see section Copy protection (Page 66)).
Removing the SIMATIC memory card
Only remove the SIMATIC memory card in POWER OFF mode of the CPU. Ensure that no
writing functions (online functions with the programming device, e.g. loading/deleting a block,
test functions) were active before POWER OFF.
If you remove the SIMATIC memory card during a write process, the following problems can
occur:
● The data content of a file is incomplete.
● The file is no longer readable, or no longer exists.
● The entire content of the card is corrupted.
Inserting the SIMATIC memory card in the CPU in STOP mode triggers a re-evaluation of
the SIMATIC memory card. The CPU hereby compares the content of the configuration on
the SIMATIC memory card with the backed-up retentive data. If the backed-up retentive data
matches the data of the configuration on the SIMATIC memory card, the retentive data is
retained. If the data differs, the CPU automatically performs a memory reset (which means
the retentive data is deleted) and then goes to STOP.
Removing the SIMATIC memory card from Windows computers
If you are using the card in a commercially available card reader under Windows, use the
"Eject" function before you remove the card from the card reader. If you remove the card
without using the "Eject" function, you may lose data.
94
File structure
Description
Job file
Panel backup files
Protected file (required to use panel backup files in STEP 7)
Protected system file (required in order to use the card)
Protected system file (required in order to use the card)
Service data file
Further files with different formats that you can also store in fold-
ers of the SIMATIC memory card
CPU 1516pro-2 PN (6ES7516-2PN00-0AB0)
Operating Instructions, 09/2016, A5E35873416-AA