HORIZONTAL
POSITION - DRAIN PAN
COIL ACCESS
PANEL
VAPOR LINE
HORIZONTAL POSITION -
SECONDARY DRAIN
VERTICAL OR
HORIZONTAL POSITION -
PRIMARY DRAIN
FIGURE 3: Component Location - Cased Coil CM Model
LIMITATIONS
These coils should be installed in accordance with all national and local
safety codes. Refer to Table 3.
TABLE 3: Coil Air Flow Limits
1
Outdoor Unit
Coil
Tons
Size
18
1-1/2
24
2
25#
2
30
2-1/2
36
3
37#
3
38#
3
42
3-1/2
48
4
49#
4
50#
4
60
5
60,64
5
61#
5
1. Asterisk (#) denotes coils only available with Factory Mount EEV.
SECTION III: COIL INSTALLATION
DUCT FLANGES
Three duct flanges are provided to attach ductwork to the coil. The
flanges are included in the parts bag along with three tie plates. Tie
plates are used to secure the coil to the furnace or to the modular air
handler as shown in Figures 5, 6, 8, 9, 11, & 12. Using the screws
included in the parts bag, duct flanges are attached as shown in Figure
4 (to secure the duct to the coil). If the flanges are not used, they may
be discarded.
4
LIQUID LINE
VERTICAL POSITION -
SECONDARY DRAIN
A0268-001
CFM Limits
Minimum
Maximum
525
675
700
900
225
900
875
1125
1050
1350
325
1350
325
1350
1225
1575
1400
1800
425
1800
425
1800
1600
1800
1750
2250
500
2250
FIGURE 4: Duct Flanges - Coils CF / CM
FIGURE 5: Vertical Applications with Furnaces
Downflow (CF/CM) or Horizontal Right (CM):
The coil cabinet has a factory installed transition angle on the bottom
front side of the cabinet. For downflow and horizontal applications with
a furnace, this angle must be repositioned to the top front side of the
cabinet.
1. Remove two screws that fasten transition angle to bottom front of
cabinet.
2. Remove two screws from top front side of cabinet.
3. Remove transition angle, rotate angle 180
to top front side of cabinet.
4. For installation with modular air handling unit, remove the transition
angle, and discard it.
AIR
HANDLER
COIL
UPFLOW
FIGURE 6: Vertical Applications with Modular Air Handlers
°
end for end, and secure
TIE PLATE
COIL
AIR
HANDLER
DOWNFLOW
Johnson Controls Unitary Products
TIE
PLATE
A0300-001