Installation Verification; Communicating Port Of The Ecm Modular Blower Control Board; Communicating Port Of The Furnace; Wiring Diagram - Eev - York CF18A Installation Manual

Cf series cm series full-cased upflow/counterflow for cooling/heat pumps
Table of Contents

Advertisement

5292154-UIM-A-0317
TABLE 4: Air Flow Data - Static Pressure Drop for CM Models
CFM @ Static Pressure Drop - IWG
1
Coil
Size
0.1
0.2
CM18A
500
700
CM18B
670
960
CM24A
490
710
CM24B
760
1050
CM24C
910
1330
CM25B
710
1020
CM30A
520
750
CM30B
670
1000
CM30C
970
1410
CM30D
1180
1720
CM36A
520
740
CM36B
710
1020
CM36C
980
1420
CM36D
1210
1750
#
710
1020
CM37B
#
980
1420
CM37C
CM38B
TBD
TBD
#
690
1150
CM38C
CM42C
970
1420
CM42D
1190
1730
CM48C
970
1450
CM48D
1250
1820
#
690
1150
CM49C
#
970
1410
CM49D
#
990
1440
CM50C
#
940
1470
CM50D
CM60C
910
1551
CM60D
1220
1730
#
990
1440
CM61C
#
940
1470
CM61D
CM64D
970
1540
1. Asterisk # denotes coils only available with Factory Mount EEV.
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recom-
mended. Applications above 0.5" are not recommended.
12
(Based on dry coil)
0.3
0.4
0.5
0.6
840
997
1115
1221
1180
1340
1498
1641
850
980
1096
1200
1330
1520
1699
1862
1640
1820
2035
2229
1210
1420
1588
1739
950
1040
1163
1274
1230
1340
1498
1641
1710
1940
2169
2376
2100
2360
2639
2890
920
1040
1163
1274
1210
1420
1588
1739
1690
1960
2191
2400
2150
2420
2706
2964
1210
1420
1588
1739
1690
1960
2191
2400
TBD
TBD
TBD
TBD
1420
1630
1820
1990
1750
1940
2169
2376
2130
2380
2661
2915
1910
1940
2169
2376
2250
2500
2795
3062
1420
1630
1820
1990
1740
2050
2290
2510
1700
1950
2180
2390
1890
2170
2430
2660
1930
1820
2035
2229
2140
2440
2728
2988
1700
1950
2180
2390
1890
2220
2490
2720
1800
1940
2169
2376
TABLE 5: Air Flow Data - Static Pressure Drop for CF Models
Coil
Size
0.1
0.7
CF18A
515
1319
CF18B
700
1773
CF24A
500
1296
CF24B
780
2011
CF24C
950
2408
CF30A
540
1878
CF30B
690
1376
CF30C
1000
1773
CF30D
1230
2566
CF36A
540
3122
CF36B
740
1376
CF36C
1020
1878
CF36D
1250
2593
CF42B
750
3201
CF42C
1010
1878
CF42D
1240
2593
CF48C
1010
TBD
CF48D
1300
2150
CF60C
950
2566
CF60D
1270
CF64D
1010
3148
2566
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recom-
3307
mended. Applications above 0.5" are not recommended.
2150
SECTION XI: INSTALLATION
2710
VERIFICATION
2580
Prior to and during the accomplishment of the installation procedures,
2870
verify all tasks are accomplished as illustrated in Figures 4 - 19.
2408
3228
THERMAL EXPANSION VALVE (TXV) CHECK LIST
2580
Is coil metering device installed correctly?
2940
Was correct TXV installed per the outdoor unit Technical Guide?
Is TXV temperature bulb positioned correctly?
2566
Is TXV temperature bulb insulated?
Is equalizer line connected?
WERE THE PRIMARY AND SECONDARY DRAINS TRAPPED CORRECTLY?
PRIMARY
PREMADE TRAPS
FIGURE 24: Drain Traps
CFM @ Static Pressure Drop - IWG
(Based on dry coil)
0.2
0.3
0.4
0.5
720
870
1030
1152
1000
1220
1400
1565
730
880
1000
1118
1090
1380
1560
1744
1380
1700
1900
2124
780
990
1080
1207
1040
1280
1380
1543
1470
1780
2000
2236
1790
2180
2460
2750
770
960
1080
1207
1060
1250
1480
1655
1470
1260
2040
2281
1820
2330
2500
2795
1100
1370
1500
1677
1470
1810
2020
2258
1790
2210
2480
2773
1500
1980
2020
2258
1890
2340
2600
2907
1600
2000
1900
2124
1800
2220
2540
2840
1590
1870
2020
2258
PLUG
(UNUSED
SECONDARY
DRAIN)
SECONDARY
HANDMADE TRAP
Johnson Controls Unitary Products
0.6
0.7
1261
1363
1715
1852
1225
1323
1911
2064
2327
2513
1323
1429
1690
1826
2449
2646
3013
3254
1323
1429
1813
1958
2498
2699
3062
3307
1837
1984
2474
2672
3037
3281
2474
2672
3184
3439
2327
2513
3111
3360
2474
2672
3" MINIMUM
A0272-001