Running Network Diagnostics on the 7845i-GSM

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
Running Network Diagnostics on the 7845i-GSM
The network diagnostic process tests the integrity of the links between the 7845i-GSM and
the various connection points of AlarmNet Control that are known as "Redirs".
To initiate the network diagnostics, press the [F] key on the 7720P Programming Tool.
NOTE: The test is performed ONLY if a physical link is detected. If no physical link is
detected, the test is aborted and the following is displayed:
If a physical link is detected, the diagnostics are performed. The following shows the
progression of the test:
NO PHYSICAL LINK
Testing Redir 1
Testing Redir 2
Reached Gateway
Redir 1
Service OK
Testing Redir 2
Redir 2
Service OK
Testing Redir 3
Redir 3
Service OK
Network Diagnostics
The first step of the test traces the connection to Redir 1
at AlarmNet Control.
A successful trace to Redir 1 is indicated here. See below
for possible errors that may occur at this stage of
testing.
The service at AlarmNet Control on Redir 1 is
functioning. See below for possible errors that may occur
at this stage of testing.
The first step of the test traces the connection to Redir 2
at AlarmNet Control.
The service at AlarmNet Control on Redir 2 is
functioning. See below for possible errors that may occur
at this stage of testing.
The first step of the test traces the connection to Redir 3
at AlarmNet Control.
The service at AlarmNet Control on Redir 3 is
functioning. See below for possible errors that may occur
at this stage of testing.