PROMPTS
Direct Wire Addr
15
(28)_
Supervision
16
(24 Hours)_
GSM Rollover Y/N
17
(Y)_
GSM 24Hr Tst Y/N
18
(N)_
Old Alarm Time
19
(10 Minutes)_
IP Flt Time
20
(60 mins)_
GSM Flt Time
21
(60 mins)_
4204/
ZONE
ENTRY
2-4204
TRIG.
[01-30]
• 30 Day
• 24 Hrs
• None
[Y], [N]
[Y], [N]
• 10 Min
• 15 Min
• 30 Min
• 1 Hr
• 2 Hrs
• 4 Hrs
• 8 Hrs
• 12 Hrs
• 24 Hrs
[01-99]
[01-99]
Section 3: Programming the 7845i-GSM
OPTIONS
When using Direct Wire downloading, the
7845i-GSM communicates with the panel as an
alpha keypad to initiate the direct wire download
session. Enter the appropriate device address.
NOTES:
1. This address must also be programmed as an
alpha keypad in the control panel (Device
Programming Mode). DO NOT connect an
actual keypad (or any other device) assigned to
this address.
2. This address must be unique from the "Device
Address" entered in Prompt 13, and cannot
equal that device address plus 1 (one) if using
2-4204 mode.
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies
the central station that a communication failure
has occurred. (If the supervision period is changed
after registration, you must re-register the
module.)
Press the [space] key to scroll through choices.
UL NOTE: Must be set to 24 hours.
If enabled, all messages (including AlarmNet
network supervisory messages) are sent over the
GSM network in the event of an Internet failure.
If disabled, all messages (except AlarmNet network
supervisory messages) are sent automatically over
the GSM network in the event of an Internet
failure.
If enabled, the 7845i-GSM sends a message once a
day to verify radio operation. A "secondary
communication path loss" message is generated if
the message is not successfully delivered.
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
UL NOTE: Must be set to 10 minutes.
In the event there is a loss of contact with the
network over the Ethernet connection, enter the
time delay (in minutes) before the 7845i-GSM
notifies the central station. IP failure will always
be sent to the central station as Primary
Communication Path Failure.
UL NOTE: Must be two (02) minutes.
In the event the module detects a communication
path failure, enter the time delay (in minutes)
before the 7845i-GSM notifies the central station.
A GSM failure will always be sent to the central
station as Secondary Communication Path Failure.
UL NOTE: Must be two (02) minutes.
DESCRIPTION
3-11