How To Undo Forcing Changes And Return The Ied To Normal Operation; Undo Forcing By Using Testmode Component; Undo Forcing By Using Lhmi; Undo Forcing By Using Pcm600 - ABB RELION 650 Series Commissioning Manual

Transformer protection
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Section 9
Testing IED operation
To force more signals, click the button
9.8.4
How to undo forcing changes and return the IED to normal
operation
Regardless of which input/output signals have been forced, all forced signals will return to
their normal states immediately when the IED is taken out of test mode.
9.8.4.1

Undo forcing by using TESTMODE component

If the IED test mode was entered through the test mode function block:
1.
This immediately undoes all forcing, regardless of how it was accomplished and disabled
all the way to force signals.
9.8.4.2

Undo forcing by using LHMI

If the IED test mode was enabled to using the LHMI:
1.
2.
This immediately undoes all forcing, regardless of how it was accomplished and disabled.
9.8.4.3

Undo forcing by using PCM600

1.
Uncheck
IEC15000031 V1 EN-US
2.
Click
56
Regardless if the forcing changes are commited or canceled, the forcing is still
active.
When the forcing is removed by exiting from IED test mode, both input and
output signals may change values. This means that logic input signals may
activate functions in the IED and that output relays may change state, which
can be potentially dangerous.
Deactivate the control input on that block.
IEDTestMode to Off in the LHMI menu.
Set
Exit from the menu and click
Forcing Session under the menu IED .
Yes in the confirmation dialogue box.
Start editing signal value for forcing again.
Yes in the Save dialogue box.
1MRK 504 160-UEN A
GUID-00E2BAD8-A29E-4B9D-80E6-E12F59E019BD v1
GUID-CA5CCA57-DFFF-4362-AC1D-08738D2BA45F v2
GUID-55199606-E70D-49B1-885D-251700FB562B v1
GUID-CE7FD186-99FC-41C8-910F-894A57037777 v1
Commissioning manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ret650

Table of Contents