Carrier 38XTZ 007-024 Installation, Operation And Maintenance Instructions page 19

Split system air-cooled
Table of Contents

Advertisement

40ABZ 020
Fig. 15 - Fan curves (standard)
Standard drive data
Motor:
4,048 kW
Pulleys: -
Motor: Ø 150; Shaft Ø 28
-
Fan: Ø 175; Shaft Ø 25
Standard motor pulley opening: 3.5 turns open
1- Closed
2- 1 turn open
3- 2 turns open
Motor pulley control
(Standard drive)
Air flow
Nominal air flow
Wet coil
Air flow: 2972 l/s
Static pressure: 185 Pa
Dry coil
Motor pulley control
(Standard drive)
Air flow
Standard motor pulley drive
4- 3 turns open
5- 4 turns open
6- 4.5 turns open
Dry coil
Air flow: 2972 l/s
Static pressure: 230 Pa
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents