Carrier 38XTZ 007-024 Installation, Operation And Maintenance Instructions page 17

Split system air-cooled
Table of Contents

Advertisement

40ALZ 014
Fig. 13 - Fan curves (standard)
Standard drive data
Motor:
2,208 kW
Pulleys: -
Motor: Ø 100; Shaft Ø 28
-
Fan: Ø 150; Shaft Ø 25
Standard motor pulley opening: 2 turns open
1- Closed
2- 1 turn open
3- 2 turns open
Motor pulley control
(Standard drive)
Air flow
Wet coil
Air flow: 2894 l/s
Static pressure: 115 Pa
Dry coil
Motor pulley control
(Standard drive)
Air flow
Standard motor pulley drive
4- 3 turns open
5- 4 turns open
Nominal air flow
Dry coil
Air flow: 2694 l/s
Static pressure: 114 Pa