To aid the regular flow of the condensation, it is advised to install the apparatus with a 3 mm inclination towards the
condensation outlet.

13.6 Duct connection

IMPORTANT: IT IS IMPORTANT NOT TO PLACE
IN OPERATION THE UNIT MINIAIR+ IF THE
MOUTHS OF THE FANS ARE NOT DUCTED OR
NOT PROTECTED BY A SAFETY NET
ADHERING WITH REGULATION UNI 9219 OR
SUCCESSIVE.
The Ducts must be the correct dimension based on the functions of system and the air diffusion characteristics
of the unit fans. A mistaken calculation of the ducting will cause power loss or the intervention of any eventual
devices present on the system.
To prevent the formation of condensation and cut down the sound level it is advised to use internally lined
Ducts.
To avoid the transmission of machine vibrations into the environment, it is advised to fit an anti-vibration joint
between the fans and Ducts. The electrical continuity must be guaranteed between the Ducts and the apparatus
via an earth cable.