Electrical Connection - Lennox MiniAir 10 Installation, Operating And Maintenance Manual

Compact air handling unit
Table of Contents

Advertisement

The trap must have a tap for correct cleaning of the lower part, and must allow an easy disassembly.
The path of the condensation drainage tube must always have a gradient toward external.
Insure that the condensation run-off tube does not interfere with discharge of the unit.
4.8.2 Water humidifier connection
The evaporative pack section is feeded by water public network (no water pump inside); the feeding system must provide
a valve (supplied by the installer) for the adjustment of the water flow; an excessive quantity may overflow the driptray
system present in the system.
For the drainage of the water and the realisation of the trap, see previous paragraph; furthermore it is recommended to
not reduce the diameter of the drainage tube till the sewer outlet, so as to avoid overflow and nasty odours.
4.9 Electrical connections
Before starting any operation, insure
that the general power supply has
been switched off.
Qualified personnel according to the supplied schemes must carry out the electrical connections at the control
panel.
Insure that the voltage and the frequency shown on the technical plate correspond to the connecting power
supply.
Connect the unit and its accessories using
adequate wiring for the used power while
respecting
dimension of the wiring must be enough to
support a voltage drop in start up phase lower
than 3% of the nominal one.
For the general power supply of the unit and its accessories, the use of adapters, multiple plugs and extension
leads is to be avoided.
It is the responsibility of the installer to insure that the installation of the unit is as close as possible to
the mains power supply, or sufficiently close to protect the electrical parts.
Connect the unit to an efficient power point, using the correct screws as supplied with the unit.
IOM / MINIAIR-0507
the
country
regulations.
The
11