5.2.3

Internal relay (M)

The internal relay (M) is a device for auxiliary relays used in the CPU module. All of the internal relay are set to off
when:
• the CPU module is powered off and then on,
• the CPU module is reset, or
• the latch clear is executed. (
The internal relay cannot be latched (data retention during power failure). Use the latch relay (L) when latch is required.
(
Page 232, Section 5.2.4)
5.2.4

Latch relay (L)

The latch relay (L) is a device for auxiliary relays that can be latched inside the CPU module. During power failure, on/
off information are retained by the battery in the CPU module. The previous on/off information are retained even after
performing the following to the CPU module.
• Power OFF→ON
• Reset
The latch relay is turned off by the latch clear operation.
Scan time is prolonged when the latch relay is used. (
5.2.5

Link relay (B)

The link relay is an internal relay whose point is input in hexadecimal.