Mitsubishi L02CPU User Manual page 132

Melsec-l series
Hide thumbs Also See for L02CPU:
Table of Contents

Advertisement

(b) On/Off of the special relay
The execution status of the sampling trace can be checked by the special relay.
SM800
(Trace preparation)
SM801
(Trace start)
SM802
(Trace execution in progress)
SM803
(Trace trigger)
SM804
(After trace trigger)
SM805
(Trace completed)
Also, if SM801 (Trace start) is turned off during sampling trace, execution of the sampling trace will be
interrupted. When the sampling trace is interrupted, the trace count is cleared.
SM800
(Trace preparation)
SM801
(Trace start)
SM802
(Trace execution in progress)
SM803
(Trace trigger)
SM804
(After trace trigger)
SM805
(Trace completed)
*1
SM801 also turns off when the sampling trace is interrupted by a programming tool.
130
Trigger condition
Trace start requested
established
Total number of traces
Trigger condition
Trace start requested
established
Total number of traces
Trace completed after performed
by the number of times set in
"Count after trigger"
Number of traces
after trigger
Trace completed after performed
by the number of times set in
"Count after trigger"
Number of traces
after trigger