Power Supply Primary Power Connections - Lincoln Electric spirit II 150 Technical Manual

Automatic plasma cutting system with fineline high definition technology
Hide thumbs Also See for spirit II 150:
Table of Contents

Advertisement

Spirit II User's Manual

Power Supply Primary Power Connections

** Before connecting primary power, check the data plate
A primary disconnect switch, switching all ungrounded supply conductors, should be
provided for each Spirit system. The disconnect switch should be located as close as
possible to the power supply so it can be turned off quickly in case of an emergency.
The disconnect switch must be equipped with time delay fuses only. The magnetic
inrush current of the power supply can be up to 30 times the steady state load current
for 0.01 seconds and up to 12 times for 0.1 sec. With non-delay fuses, the fuse will
clear due to the inrush current. The same applies for circuit breakers which have an
instantaneous magnetic trip.
recommended if time delay fuses are not used or allowed by local or national codes.
The main feed device (breaker or fuse) and any branch protection (breaker or
fuse) upstream of the power supply must be sized to handle all branch loads for
both steady state and inrush current.
The disconnect switch should be sized according to local and national codes. The
rating must meet or exceed the continuous rating of the fuses used. See the following
chart for recommended fuse sizes:
3 Phase
Input Voltage (VAC)
208 VAC, 60Hz
220 VAC, 60Hz
240 VAC, 60Hz
380 VAC, 50/60Hz
400 VAC, 50/60Hz
415 VAC, 50/60Hz
440 VAC, 50/60Hz
480 VAC, 60Hz
600 VAC, 60Hz
Connection to the supply circuit can be by means of flexible supply cables or supply
cables through conduit to a permanent installation. The supply cables should have a
600 volt minimum rating and should be sized according to local and national codes.
Route flexible supply cables through the strain relief on the back of the power supply
and connect to the input terminal block TB5 as shown. For supply cables through
conduit, install the conduit in place of the strain relief and connect the associated supply
cables to the input terminal block TB5. See Figure 3 on the next page.
TB5 is located on the rear of the power supply and is accessible with the right-side
This information is subject to the controls of the Export Administration Regulations [EAR]. This information shall not be provided to
non-U.S. persons or transferred by any means to any location outside the United States contrary to the requirements of the EAR.
on the power supply to verify the voltage required **
Use of a motor-start circuit breaker or equivalent is
Input Current at
Maximum
Output (amps)
99
94
86
54
52
50
47
43
34
Recommended
Time-Delay Fuse
Size (amps)
125
125
110
65
65
60
60
60
45
3-7
Section 3: Installation

Advertisement

Table of Contents
loading

Table of Contents