IPID Function Block
This function block diagram shows the arguments in the IPIDCONTROLLER
function block.
IPIDCONTROLLER
IPIDCONTROLLER
EN
Process
SetPoint
FeedBack
Auto
Initialize
Gains
AutoTune
ATParameters
The following table explains the arguments used in this function block.
IPIDCONTROLLER Arguments
Parameter
Parameter
Type
EN
Input
Process
Input
SetPoint
Input
Feedback
Input
Auto
Input
Initialize
Input
Gains
Input
AutoTune
Input
ENO
Output
AbsoluteError
ATWarning
OutGains
Data Type Description
BOOL
Function block enable
When EN = TRUE, execute function.
When EN = FALSE, do not execute function.
Only applicable to LD, EN is not required in FBD
programming.
REAL
Process value, measured from the output of controlled
process.
REAL
Set point value for desired process
REAL
Feedback signal, measured from control input to a
process.
BOOL
Operating modes of PID controller:
• TRUE —controller runs in normal mode
• FALSE — controller out value equals to
feedback value
BOOL
A change in value (True to False or FALSE to TRUE)
causes the controller to eliminate any proportional
gain during that cycle. It Also initializes AutoTune
sequences.
GAIN_PID
Gains for IPIDCONTROLLER
See GAIN_PID Data type
BOOL
Start AutoTune sequence
D
Appendix
157