Mitsubishi QJ71MB91 User Manual page 68

Table of Contents

Advertisement

4
MODBUS(R) STANDARD FUNCTIONS
Start
Address field
:
2 characters
(3A
)
H
Remark
4
- 13
4.2 Frame Specifications
4.2.1 Frame mode
Address field
Function code
(02
)
H
Figure 4.3 Frame for CRC calculation
(b) ASCII mode
In this mode, frames are received or sent in units of 2 characters (2 bytes) in
ASCII codes.
The frame specifications are compliant with the MODBUS
specifications.
Function code
2 characters
Error check calculation range
Figure 4.4 Frame in ASCII mode
The error check in the ASCII mode is conducted by LRC (Longitudinal
Redundancy Check).
The QJ71MB91 calculates the LRC by the following steps.
Please follow the same steps to calculate the LRC when conducting an error
check on the target device.
1) To calculate the LRC, convert the ASCII codes within the error check range
into the RTU format (binary).
2) Add the figures in units of contiguous 8 bits in the frame. (Excluding carries
during addition.)
3) Change the result of the above 2) to a 2's complement. (Reverse the bits and
add 01
.)
H
4) Convert the result of 3) to an ASCII code.
CRC (Error check)
(07
)
(41
)
H
H
Data
n x 2 characters
(n = 0 to 252)
(12
)
H
protocol
Error check
END
CR + LF
2 characters
(0D
) (0A
H
H
)