7
PARAMETER SETTING
(3) Parameter setting procedure
Set the parameters by the following procedure.
YES
Check the auto-refresh parameters,
the head input/output numbers, etc.
Start
Set parameters with
GX Configurator-MB?
YES
Set the intelligent function module
R
switch's MODBUS
device
assignment parameter starting
method (switch 2, bit 0) to ON.
(
Section 6.6)
Set function parameters to be used.
Automatic communication parameters
(
Section 8.4.1)
R
MODBUS device assignment parameters
(
Section 8.4.2)
Automatic refresh settings
(
Section 8.5)
Write parameters to the
programmable controller CPU.
With the RUN/STOP switch set to
RUN, reset the programmable
controller CPU.
SP.PARA ERROR
occurred in the
programmable
controller CPU?
NO
(To next page)
Figure 7.1 Parameter setting procedure
7.1 Parameter Settings and Setting Procedure
NO
Change MODBUS
assignment?
YES
Set the intelligent function module
switch's MODBUS device
R
assignment parameter starting
method (switch 2, bit 0) to ON.
(
Section 6.6)
Create a sequence program for parameter
setting of functions to be used.
Automatic communication parameters
(
Section 9.1.1, 9.2.1)
R
MODBUS device assignment parameters
(
Section 9.1.2, 9.2.2)
After writing the sequence
program to the programmable
controller CPU, reset the
programmable controller CPU
Put the programmable controller
CPU into the RUN status
R
NO
device
1)
7