Fisher 3570 Instruction Manual page 13

Pneumatic valve positioners
Hide thumbs Also See for 3570:
Table of Contents

Advertisement

Instruction Manual
D200137X012
Figure 5. Bellows Mounting for Direct and Reverse Action
2
BEAM
1
BELLOWS BASE
PEDESTAL
1—MOUNTING SCREW
2—MOUNTING SCREW
3—BELLOWS POST
A1088‐1
WARNING
The following procedures require taking the positioner, actuator, and control valve assembly out of service. To avoid
personal injury or property damage caused by uncontrolled process pressure, provide a temporary means of control for the
process before taking the assembly out of service.
Before removing the input signal and supply pressure connections from the positioner, remove the input signal and supply
pressure sources from the connections. The sudden release of pressure can cause personal injury or property damage.
Note
Changing the positioner action might require changing the bias spring and/or the spring retainer. Contact your
Management sales office
for assistance in determining if a new bias spring and/or spring retainer are required. Refer to instruction
manual supplement D104021X012.
Changing to Reverse Action
1. Bypass the control valve and shut off the input signal line and the supply pressure line to the positioner.
2. Loosen the four thumb screws on the underside of the positioner base and remove the cover.
2
1
BELLOWS TOP VIEW
WITH OPTIONAL RE­
STRICTOR
1
2
2
3
1
DIRECT
REVERSE
ACTION
ACTION
RESTRICTOR
2
1
BELLOWS BASE
2
BEAM
3
PEDESTAL
3570 Positioners
September 2015
Emerson Process
13